General Specifications - PLCS Ethernet

Items

Specifications

Standards

Op. Temp.

-10 ~ 65℃

-

St. Temp.

-25 ~ 80℃

-

Op. Hum.

5 ~ 95 % RH, Not condensed

-

St. Hum.

5 ~ 95 % RH, Not condensed

-

Vibration

In case of Intermittent Vibration

-

Frequency

Acceleration

Amplitude

Sweep

IEC61131-2

5 = f < 9 Hz

-

3.5 mm

10 times

in X, Y, Z

9 = f = 150 Hz

9.8m/s2  {1G}

-

In case of Continuous Vibration

Frequency

Acceleration

Amplitude

Sweep

5 = f < 9 Hz

-

1.75 mm

10 times

in X, Y, Z

9 = f = 150 Hz

4.9m/s2  {0.5G}

-

Shock

· Max. shock Acc.: 147 m/s2  {15G}

· Time: 11 ms

· Pulse wave: Half sine wave pulse (3 times each in X, Y, Z)

IEC61131-2

Noise

Square Wave

Impulse Noise

2 kV

CIMON

Standard

Electrostatic

Discharge

2 kV (contact), 8 kV (air)

IEC61131-2

IEC61000-4-2

Radiated

Electromagnetic

Field

80 ~ 1000 MHz, 10 V/m

IEC61131-2

IEC61000-4-3

Fast Transient

Burst Noise

(Voltage)

CPU, Power

2 kV

IEC61131-2

IEC61000-4-4

Digital/Analog I/O (AC)

Digital/Analog I/O (DC)

1 kV

Communication

Ambient

Conditions

No corrosive gas and no dust

Altitude

2,000 m or less

Pollution

2 or less

Cooling

Natural air cooling