Understanding Pulse Input Method and Counting Method - PLCS HSC

Understanding Pulse Input Method and Counting Method - PLCS HSC

Type of Pulse Input Method ,

Pulse Input Method

Count Timing

1-phase

1-multiple

Counting

image-20240326-062844.png

A module counts at the rising edges of A.

B is off.

Counting Down

image-20240326-062851.png

A module counts at the falling edges of A.

B is on.

1-phase

2-multiple

Counting

image-20240326-062855.png

A module counts at the rising and falling edges of A.

B is off.

Counting Down

image-20240326-062859.png

A module counts at the rising and falling edges of A.

B is on.

CW/CCW

Counting

image-20240326-062906.png

A module counts at the rising edges of A.

B is off.

Counting Down

image-20240326-062911.png

A is off.

A module counts at the rising edges of B.

2-phase

1-multiple

Counting

image-20240326-062916.png

When B is off, a module counts at the rising edges of A.

Counting Down

image-20240326-062921.png

When B is off, a module counts at the falling edges of A.

2-phase

2-multiple

Counting

image-20240326-062927.png

When B is off, a module counts at the rising edges of A.

When B is on, a module counts at the falling edges of A.

Counting Down

image-20240326-062937.png

When B is on, a module counts at the rising edges of A.

When B is off, a module counts at the falling edges of A.

2-phase

4-multiple

Counting

image-20240326-062941.png

When B is off, a module counts at the rising edges of A.

When B is on, a module counts at the falling edges of A.

When A is on, a module counts at the rising edges of B.

When A is off, a module counts at the falling edges of B.

Counting Down

image-20240326-062947.png

When B is on, a module counts at the rising edges of A.

When B is off, a module counts at the falling edges of A.

When A is off, a module counts at the rising edges of B.

When A is on, a module counted at the falling edges of B.

 

1-phase Pulse Input

1-multiple or 2-multiple can be selected. The relation between Phase A and counting down is as follows.

 

image-20240326-062816.png

 

CW/CCW Pulse Input

If there is pulse input in Phase A, the module counts. If there is pulse input in Phase B, the module counts down. The relation between Phase A and Phase B is as follows.

 

image-20240326-062819.png

 

2-phase Pulse Input

1-multiple or 2-multiple or 4-multiple can be selected. It is decided whether the module counter or counts down by the difference between Phase A and Phase B. The relation between Phase A and Phase B is follows.

 