Setup range of digital conversion value to output Raw value. 2 bit for each channel is assigned.
[Bit Mapping: 16 bits]
MSB LSB
0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | CH4 | CH3 | CH2 | CH1 |
Code | Normal input range | Full Range |
00 (0) | -8000 ~ +8000 | -8191 ~ +8192 |
01 (1) | -8000 ~ +8000 | -8000 ~ +8000 |
10 (2) | -192 ~ 16191 | -192 ~ 16191 |
11 (3) | 0 ~ 64000 | 0 ~ 64000 |
Full Range: It is used for Exceeding of normal input range.