IEC 61850 Settings

IEC 61850 Settings

IEC61850 Settings

Select CIMON IEC61850 Client.

image-20241016-071947.png

Process for adding IEC61850 driver is as follows:

1. Set station name

2. Select station addition method

3. Read IED

4. Select DA

 

When adding a station, first set the station name and then select the addition method. ‘Read from IED’ method is directly connecting to the relay to read IED tree data. ‘Read from CID’ method is reading CID file.

image-20241016-073744.png
Set station name
image-20241016-073255.png
Select station addition method

 

The following IEC61850 driver settings window will appear:

The IP address and port refer to the relay's IP address and port. If you have selected the relay connection method, the "Connect" and "Read" buttons will be activated, allowing you to click the "Read" button after establishing the connection.

image-20241016-073922.png

Connect to relays

When adding the driver, the IED tree is read by directly connecting to the relay.

After entering the IP address and port in the connection settings section, clicking "Connect" will automatically read the IED tree.

image-20241016-073834.png

 

When you select the Data Attribute(DA) to be used in the project, it will be added to the list on the right.

image-20241016-073822.png

After clicking 'Ok' to complete the settings, the selected Data Attribute(DA) will be automatically registered as tags in a tree format.

Additionally, when modifying or deleting a station, the tags will be automatically updated or removed.

image-20241016-073953.png
  • Do not modified IEC61850 tags

  • Close UA Runtime when modifying driver.