MITSUBISHI MELSEC Ethernet

 

 

Description

Note

Distributor

MITSUBISHI

 

Device

MELSEC NET

 

Comm. Module

 

 

Comm. Method

RS232

 

Protocol

MC Protocol 3E

 

Comm. Frame Display

Not supported

 

Read after write

Supported

 

 

To communicate with UltimateAccess Web, MELSECNET/H board must be mounted to the PC’s PCI slot and MNETH Utility software must be installed beforehand.

 

Communication Settings

 

  1. Station

 

Channel Type: Select the type of the channel based on the MELSECNET/10’s slot location.

 

 

  1. COM Block

 

Station Type: Select the station.

Own Station - Station of MELSECNET/10.

Other Station – Other station.

 

Network No.        Sets the target network number if other station is selected.

Station No.          Sets the target station number if other station is selected.

 

Address                  Sets the starting address and the amount of words to communicate in one block.

 

Address Format

Word addresses (W,D…)

[Network No.]:[Station No.][Address Type][Address]

Ex) 00:FFW0 -> Network number 0, 255th station’s W device, address 0.

Bit addresses

[Network No.]:[Station No.][Address Type][Address].[Bit Location]

Ex) 00:FFW0.F -> Network number 0, 255th station’s W device, address 0, 16th bit

  • Writing to a word device using bit address format is not available.