MITSUBISHI MELSEC Ethernet
Â
 | Description | Note |
Distributor | MITSUBISHI | Â |
Device | MELSEC NET | Â |
Comm. Module | Â | Â |
Comm. Method | RS232 | Â |
Protocol | MC Protocol 3E | Â |
Comm. Frame Display | Not supported | Â |
Read after write | Supported | Â |
Â
To communicate with UltimateAccess Web, MELSECNET/H board must be mounted to the PC’s PCI slot and MNETH Utility software must be installed beforehand.
Â
Communication Settings |
Â
Station
Â
Channel Type: Select the type of the channel based on the MELSECNET/10’s slot location.
Â
Â
COM Block
Â
Station Type:Â Select the station.
Own Station - Station of MELSECNET/10.
Other Station – Other station.
Â
Network No.       Sets the target network number if other station is selected.
Station No.         Sets the target station number if other station is selected.
Â
Address                 Sets the starting address and the amount of words to communicate in one block.
Â
Address Format
Word addresses (W,D…)
[Network No.]:[Station No.][Address Type][Address]
Ex) 00:FFW0 -> Network number 0, 255th station’s W device, address 0.
Bit addresses
[Network No.]:[Station No.][Address Type][Address].[Bit Location]
Ex) 00:FFW0.F -> Network number 0, 255th station’s W device, address 0, 16th bit
Writing to a word device using bit address format is not available.