Address Map

MOBUS를 사용할 경우에는 아래의 Address Map을 이용하여 CIMON-PLC Address를 Modicon Address로 변환하여 통신하여야 합니다.

 

 

 

 

Table Ver. A

Table Ver. B

Table Ver. C

Bit / Word

CIMON-PLC Address

Size

Modicon

Address

CIMON-PLC Address

Size

Modicon

Address

CIMON-PLC Address

Size

Modicon

Address

Bit Read Input

Register

X0000 ~ X255F

4096 Bits

100001 ~ 104096

Table Ver. A와 동일

X0000 ~ X511F

8192 Bits

100001 ~ 108192

F0000 ~ F127F

2048 Bits

104097 ~ 106144

F0000 ~ F127F

2048 Bits

108193 ~ 110240

T0000 ~ T1023

1024 Bits

106145 ~ 107168

T0000 ~ T4095

4096 Bits

110241 ~ 114336

C0000 ~ C1023

1024 Bits

107169 ~ 108192

C0000 ~ C4095

4096 Bits

114337 ~ 118432

Bit Read Coil

Register

Y0000 ~ Y255F

4096 Bits

000001 ~ 004096

Y0000 ~ Y511F

8192 Bits

000001 ~ 008192

M0000 ~ M511F

8192 Bits

004097 ~ 012288

M0000 ~ M999F

16000 Bits

008193 ~ 024192

K0000 ~ K127F

2048 Bits

012289 ~ 014336

K0000 ~ K999F

16000 Bits

024193 ~ 040192

L0000 ~ L127F

2048 Bits

014337 ~ 016384

L0000 ~ L999F

16000 Bits

040193 ~ 056192

Word Input Register

X0000 ~ X2550

256 Words

300001 ~ 300256

X0000 ~ X5110

512 Words

300001 ~ 300512

F0000 ~ F1270

128 Words

300257 ~ 300384

F0000 ~ F1270

128 Words

300513 ~ 300640

TC0000 ~ TC1023

1024 Words

300385 ~ 301408

TC0000 ~ TC4095

4096 Words

300641 ~ 304736

CC0000 ~ CC1023

1024 Words

301409 ~ 302432

CC0000 ~ CC4095

4096 Words

304737 ~ 308832

S0000 ~ S0049

50 Words

302433 ~ 302482

S0000 ~ S0049

50 Words

308833 ~ 308883

Word Holding Register

Y0000 ~ Y2550

256 Words

400001 ~ 400256

Y0000 ~ Y511F

512 Words

400001 ~ 400512

K0000 ~ K1270

128 Words

400257 ~ 400384

K0000 ~ K9990

1000 Words

400513 ~ 401512

TS0000 ~ TS1023

1024 Words

400385 ~ 401408

TS0000 ~ TS4095

4096 Words

401513 ~ 405608

CS0000 ~ CS1023

1024 Words

401409 ~ 402432

CS0000 ~ CS4095

4096 Words

405609 ~409704

L0000 ~ L1270

128 Words

402433 ~ 402560

L0000 ~ L9990

1000 Words

409705 ~ 410704

M0000 ~ M5110

512 Words

402561 ~ 403072

M0000 ~ M9990

1000 Words

410705 ~ 411704

D0000 ~ D9999

10000 Words

403073 ~ 413072

D0000 ~ D31999

32000 Words

403073 ~ 435072

D0000 ~ D31999

32000 Words

411705 ~ 443704

 

Bit Read Input Register, Bit Read Coil Register는 Modicon Address를 한 비트씩 차지합니다.

[예시] Read Input Register -> 100001 : X0000, 100002: X0001, ... , 100017: X0010, …

[예시] Read Coil Register -> 000001: Y0000, 000002: Y0001, ... , 000017: Y0010, …

 

Word Input Register, Word Holding Register는 Modicon Address를 한 워드씩 차지합니다.

[예시] Word Input Register -> 300001: X0000, 300002: X0010, 300003: X0020, …

[예시] Word Holding Register -> 402561: M0000, 402562: M0010, 402563: M0020, …

 

[주의] 일부 MODBUS Master 기기에서는 각 데이터 Type의 어드레스 범위중 1~9999 영역만 읽기/쓰기가 가능합니다.

          이 경우에 PLC의 데이터 중 Modicon Address 9999보다 큰 영역에 해당되는 부분을 Access 할 수 없으므로 User 프로그램상에서 조치가 필요할 수 있습니다.

[주의] TS, CS Device는 Device에 값을 '쓰기' 하는 것을 허용하지 않습니다.

 

[예시] 0번부터 맵핑하는 경우와 1번부터 맵핑하는 두가지 경우를 가정하고 XYDM 디바이스와 맵핑시킨 테이블.