CIMON-NET Master

The CIMON-NET Master program is used to configure I/O device area for controlling Remote I/O with CIMON NET Master Module (CM1-CN01M).

Registering the CIMON-NET Master program
Select [File] -> [New Program] -> [CIMON-NET Master] menu.

 

image-20240329-083209.png

 

Enter the Program Name, Program ID and Program Free Space (OnlineEdit Buffer).
Click the [OK] button.

Writing the CIMON-NET Master program
This example applies to a case when CIMON-NET Master Module (CM1-CN01M) controls Remote IO and the module is mounted on local base, slot #1.
The number of points for the Remote IO connected to the CM1-CN01M is 16 inputs and 16 outputs.

 

image-20240329-083214.png

 

 

Configure communication setup for the Master Module.
Base: Local (Default)
Slot: 1
Module Type: CM1-CN01M (Default)
Master Module Station: 0 (Default)
Baud Rate: 125 (Default)
Time out: 200 (Default)
Polling time: 10 (Default)
Click on [Write] button.

 

 

Click on [AUTO SCAN] button.

 

 

 

When the Remote I/O is detected after the [AUTO SCAN] as shown above, select [Input] tab under the [Data Block] and click on [Add] button in order to read input of the Remote I/O and save 1 Word (16bit) in M0000.

 

 

Select M for Device Type, 0 for Start Address and 1 for Buffer Size.
Click on [OK] button.

 

 

Select [Output] tab under the [Data Block] and click on [Add] button in order to set the data of 1 Word (16bit) from Y0010 as the output of the Remote I/O.

 

 

Select Y for Device Type, 10 for Start Address and 1 for Buffer Size.
Click on [OK] button.

 

 

Click on [Write] button.