RTD_M

RTD_M

 

It has digital value from RTD module and this digital value will be save in D device.  It is used to get more than two digital values if the FB name is finished with "_M".

 

 

Variable Name

I/O

Type

Device

BASE

Input

Word

Write Base number 0~16

SLOT

Input

Word

Write Slot number

CM1 : 0 ~ 11 / CM2 : 1 ~ 4 / CM3 : 1 ~ 11

ADDR

Input

Word

Write D address. (Ex. D150 : Write 150)

SIZE

Input

Word

Write number of Channel

(Ex. Ch.1 : Write 1, Ch.1~3 : Write 3)

OUTPUT

Output

Bit

When it works, it will be turned ON

 If you write wrong SLOT number or BASE number, CPU will have an error.

According to CPU type, D device address range will be different.

 

 

System Library type

  • CM1_RTD_M

  • CM2_RTD_M

  • CM3_RTD_M

 

 

Buffer Memory Index

  • CM1 RTD : 21 ~ 28 (Ch.1~8 : Digital converted value)

  • CM2 RTD : 21 ~ 28 (Ch.1~8 : Digital converted value)

  • CM3 RTD : 21 ~ 24 (Ch.1~4 : Digital converted value)

 

 

Example) CM1_RTD_M

 

Ex) Base: D00 = 1, Slot: D01 = 2, ADDR: D02 = 80, SIZE: D03 = 3

You can get 3 digital value from Ch1 to Ch3 at slot #2 in 1st expansion base and save them to D80, D81, and D82 in sequence. When it works, M05 will be turned ON.

 

 

Example) CM3_RTD_M

 

You can get 4 digital values from Ch1 to Ch4 at slot #2 and save them to D500, D501, D502, and D503 in sequence. When it works, L10 will be turned ON.

 