General Specifications(CM1 Load cell)

General Specifications(CM1 Load cell)

Items

Specification

Standards

Op. Temp

-10℃~65℃

-

St. Temp

-25℃~80℃

-

Op. Hum

5~95%RH, Not Condensed

-

St. Hum

5~95%RH, Not Condensed

-

Vibration

In case of intermittent vibration

IEC 61131-2

Frequency

Acceleration

Amplitude

Sweep

5≤f<9Hz

-

1.75mm

10 times

in X, Y, Z

9≤f≤150Hz

9.8m/s2{1G}

-

In case of continuous vibration

Frequency

Acceleration

Amplitude

Sweep

5≤f<9Hz

-

3.5mm

10 times

in X, Y, Z

9≤f≤150Hz

4.9m/s2{0.5G}

-

Shock

Max. shock Acc. : 147m/s2 {15G}

Time : 11ms

Pulse wave : Half sine wave pulse(3 times in X, Y, Z)

IEC 61131-2

Noise

Square wave

impulse noise

±2kV

CIMON

Standard

Electro-static discharge

±4kV (Contact), ±8kV (Air)

IEC 61131-2 IEC61000-4-2

Radiated

electro-magnetic field

80 ~ 1000 MHz,10V/m

IEC 61131-2 IEC61000-4-3

Fast transient

bust noise

(Voltage)

CPU, Power

2kV

IEC 61131-2 IEC61000-4-4

Digital/Analog I/O (AC)

2kV

Digital/Analog I/O (DC)

1kV

Communication

Ambient

 Conditions

No corrosive gas and no dust

Altitude

2,000m or less

Pollution

2 or less

Cooling

Natural Air Cooling

Related content

General Specifications(CM1 Dualization)
General Specifications(CM1 Dualization)
More like this
General Specifications(CM1 TC)
General Specifications(CM1 TC)
More like this
General Specifications(CM1 HSC)
General Specifications(CM1 HSC)
More like this
General Specifications(CM1 Expansion)
General Specifications(CM1 Expansion)
More like this
General Specifications(CM1 Serial)
General Specifications(CM1 Serial)
More like this
General Specifications(CM1 DO)
General Specifications(CM1 DO)
More like this