Yokogawa FA-M3

Yokogawa FA-M3

This document describes the Yokogawa FA-M3 communication driver for Canvas.

Communication Settings: Canvas

I/O Device Configuration

 

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Serial for Connection Type > select Yokogawa FA-M3 for Device Type.

 

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

Station

In this window, users can assign a Station Name and ID for the target I/O Device.

See the Serial Communication Configuration section for more information.

Address and Supported Symbols

Some memory areas have different addressing format.

  • X, Y memory area addressing format
    - Format: {symbol}{1 digit for rack number}{2 digits for slot number}{2 digits for bit number}
    - Rack number: 0 - 7
    - Slot number: 00 - 12
    - Bit number: 00 - 63

  • L memory area addressing format
    - Format: {symbol}{1 digit for rack number}{4 digits for memory address}
    - Rack number: 0 - 7
    - Memory address: 0 - 1023

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Input relay

X

X00201 - X71649

X00201 - X71664

Decimal

R

Output relay

Y

Y00201 - Y71649

Y00201 - Y71664

Decimal

R/W

Internal relay

I

I0001 - I4081

I0001 - I4096

Decimal

R/W

Shared relay

E

E0001 - E2033

E0001 - E2048

Decimal

R/W

Link relay

L

L00001 - L71008

L00001 - L71023

Decimal

R/W

Special relay

M

M001 - M497

M001 - M512

Decimal

R/W

Data register

D

-

D0001 - D5120

Decimal

R/W

Shared register

R

-

R0001 - R1024

Decimal

R/W

Index register

V

-

V01 - V16

Decimal

R/W

File register

B

-

-

-

-

Link register

W

-

W0001 - W1024

Decimal

R/W

Special register

Z

-

Z001 - Z256

Decimal

R/W

Timer relay

TU

TU001 - TU256

-

Decimal

R/W

Timer current value

TP

-

TP001 - TP256

Decimal

R

Timer current value

TI

-

TI001 - TI256

Decimal

R

Timer present value

TS

-

TS001 - TS256

Decimal

R/W

Counter relay

CU

CU001 - CU256

-

Decimal

R/W

Counter current value

CP

-

CP001 - CP256

Decimal

R

Counter current value

CI

-

CI001 - CI256

Decimal

R

Counter present value

CS

-

CS001 - CS256

Decimal

R/W

 

Communication Cable Wiring

eXT07/nXT07
COM1: RS-422/485
COM2: RS-232C

 

eXT10/12/15
COM1: RS-422/485
COM2: RS-232C
COM3: RS-232C

COM1

 

COM2

 

COM3

 

 

The above picture shows the RS-232C and RS-422/485 ports of the Xpanel. Please refer to the manual of your device for signal descriptions.

For the RS-232C ports, Xpanel provides the standard DB9 RS-232C pin assignment.