Start Operation, Series Connection, Parallel Connection for Rising-Falling Edge

 

Start Operation, Series Connection, Parallel Connection for Positive-Negative Transition Contact: LDP, LDF, ANDP, ANDF, ORP, ORF

 

Instruction

Device address

No. of Steps

Flag

M

X

Y

K

L

F

T

C

S

Z

D

@D

Int.

Error

Zero

Carry

LDP

LDF

ANDP

ANDF

ORP

ORF

S

o

o

o

o

o

o

o

o

-

-

-

-

-

1

-

-

-

 

 

 LDP (Load Pulse)

This function is used to read the positive transition contact of a circuit

If an input condition is turned ON from OFF, this turns the device ON for one scan.

 

 

 

 LDF (Load Falling Pulse)

This function is used to read the negative transition contact of a circuit.

If an input condition is turned OFF from ON, this turns the device ON for one scan.

 

 

 

 

 ANDP (AND Pulse)

This function is used to read the positive transition contact in series connection.

If an input condition is turned ON from OFF, this turns the device ON for one scan.

If the left connection is turned ON, the right connection turns ON for one scan.

 

 

 

 ANDF (AND Falling Pulse)

This function is used to read the negative transition contact in series connection.

If an input condition is turned OFF from ON, this turns the device ON for one scan.

If the left connection is turned ON, the right connection turns ON for one scan.

 

 

 

 

ORP (OR Pulse)

This function is used to read the positive transition contact in parallel connection.

If an input condition is turned ON from OFF, this turns the device ON for one scan.

If the below connection is turned ON, the above connection turns ON for one scan.

 

 

 

ORF (OR Falling Pulse)

This function is used to read the negative transition contact in parallel connection.

If an input condition is turned OFF from ON, this turns the device ON for one scan.

If the below connection is turned ON, the above connection turns ON for one scan.