General Specifications(CM3 Serial)

Items

Specification

Standards

Op. Temp.

-10℃–65℃

-

St. Temp.

-25℃–80℃

-

Op. Hum

5–95% RH, Not condensed

-

St. Hum

5–95% RH, Not condensed

-

Vibration

In case of Intermittent Vibration

IEC 61131-2

Frequency

Acceleration

Amplitude

Sweep

5 ≤ f < 9 Hz

-

3.5 mm

10 times
in X, Y, Z

9 ≤ f ≤ 150 Hz

9.8 m/s2(1G)

-

In case of Continuous Vibration

Frequency

Acceleration

Amplitude

Sweep

5 ≤ f < 9 Hz

-

1.75 mm

10 times
in X, Y, Z

9 ≤ f ≤ 150 Hz

4.9 m/s2(1G)

-

Shock

  • Max. shock Acc.: 147 m/s

2(15G)

  • Time: 11 ms

  • Pulse wave: Half sine wave pulse (3 times each in X, Y, Z)

IEC 61131-2

Noise

Square Wave
Impulse Noise

±2 kV

CIMON

Standard

Electrostatic Discharge

±4 kV (contact), ±8 kV (air)

IEC 61131-2

IEC 61000-4-2

Radiated

Electromagnetic Field

80–1000 MHz,10 V/m

IEC 61131-2

IEC 61000-4-3

Fast Transient

Burst Noise

(Voltage)

CPU, Power

2 kV

IEC 61131-2

IEC 61000-4-4

Digital/Analog I/O (AC)

Digital/Analog I/O (DC)

1 kV

Communication

Ambient Conditions

No corrosive gas and no dust

Altitude

2,000 m or less

Pollution

2 or less

Cooling

Natural air cooling