General Specifications(CM1 Dualization)

General Specifications(CM1 Dualization)

Items

Specification

Standards

Op. Temp

-10℃–65℃

-

St. Temp

-25℃–80℃

-

Op. Hum

5–95 %RH, Not condensed

-

St. Hum

5–95% RH, Not condensed

-

Vibration

In case of Intermittent Vibration

IEC 61131-2

Frequency

Acceleration

Amplitude

Sweep

5 ≤ f < 9 Hz

-

3.5 mm

10 times

in X, Y, Z

9 ≤ f ≤ 150 Hz

9.8 m/s2(1G)

-

In case of Continuous Vibration

Frequency

Acceleration

Amplitude

Sweep

5 ≤ f < 9 Hz

-

1.75 mm

10 times

in X, Y, Z

9 ≤ f ≤ 150 Hz

4.9 m/s2(1G)

-

Shock

  • Max. shock Acc.: 147 m/s2(15G)

  • Time: 11 ms

  • Pulse wave: Half sine wave pulse (3 times in X, Y, Z)

IEC 61131-2

Noise

Square Wave

Impulse Noise

±2 kV

CIMON

Standard

Electrostatic Discharge

±4 kV (Contact), ±8 kV (Air)

IEC 61131-2

IEC 61000-4-2

Radiated

Electromagnetic Field

80–1000 MHz,10 V/m

IEC 61131-2

IEC 61000-4-3

Fast Transient

Burst Noise

(Voltage)

CPU, Power

2 kV

IEC 61131-2

IEC 61000-4-4

Digital/Analog I/O (AC)

Digital/Analog I/O (DC)

1 kV

Communication

Ambient Conditions

No corrosive gas and no dust

Altitude

2,000 m or less

Pollution

2 or less

Cooling

Natural air cooling

Related content

General Specifications(CM1 HSC)
General Specifications(CM1 HSC)
More like this
General Specifications(CM1 DO)
General Specifications(CM1 DO)
More like this
General Specifications(CM1 Serial)
General Specifications(CM1 Serial)
More like this
General Specifications(CM1 Redundancy)
General Specifications(CM1 Redundancy)
More like this
General Specifications(CM1 Expansion)
General Specifications(CM1 Expansion)
More like this
General Specifications(CM1 TC)
General Specifications(CM1 TC)
More like this