OMRON CS/CJ Series Enet (FINS)
Communication Setup: Xpanel
I/O Device Configuration | To create a new device, select [Tools] → [I/O Device Editor]. Click the icon to add a new device, then select an “Ethernet” [Connection Type] and a “Omron FINS” [Device Type]. Device Name: Designate a name for the I/O Device. |
I/O Device Settings
| Once the connection type, device name, and device type have been assigned, the [I/O Device Editor] window populates with the default settings for the selected communication protocol. After selecting the correct [Connection Type] and [Device Type], match the remaining settings to the target I/O device’s communication settings. For FINS specific settings, refer to the below section. |
See the Communication Configuration section for more information.
PLC Mode
CS/CJ Series Communication Setting (Example CJ2M CPU35)
External Rotary Switch Setting
The node number shows hexadecimal on screen.
Set the UNIT number.
Set the NODE number.
Built-in EtherNet/IP Port Setting
Select [IO Table/Unit Setup] as shown below.
Select [1500] CJEIP21 (Built-in EtherNet/IP Port for CJ2M)(Unit:0) at Inner Port/Inner Board. (Select “TCP/IP” and write the IP number of the PLC EtherNet/IP at “IP Address”.
Select the [FINS/TCP] tab and choose the ‘Default’ option of the ‘FINS/TCP Port’.
Click ‘Start with Settings Inherited' as shown below.
Check the Net, Node, and Unit.
Select [Start Routing table] as shown below.
Select “Unit 00 (Ethernet/IP)” and insert CPU SIOU as shown in the picture below.
NJ5xx Series (Built-in EtherNet/IP Port)
Built-in EtherNet/IP Port Setting
Select [Controller Setup] → [Operation Settings].
Refer to the picture below and add a setting to the “Local Network Table”.
Select [Controller Setup] → [Built-in EtherNet/IP Port Settings]. Select “TCP/IP Settings” and set IP address of PLC EtherNet/IP port.
Select [FINS Settings] and set the “Node address of built-in EtherNet/IP port” and the “FINS/UDP port number” as shown below.
FINS Data Block Registration
Select [Data] → [Global Variables].
Right-click and select “Create New”.
For each item, register a Name, Data Type, and an AT (see image below).
After completing the settings, click [Controller] → [Synchronization] to download it to the PLC. Reset the PLC power just in case the download setting does not work properly.
Name: It is a variable name that is used in the PLC program.
Data Type: Register the data type of the variable. In order to easily configure the communication setting, choose “Array Type”.
AT: Register the device format through FINS communication. Refer to the table shown below.
Area | Format |
CIO Area | %0 , %10... |
Work Area | %W0, %W100... |
Holding Area | %H0, %H50... |
DM Area | %D0, %D150... |
EM Area | %E0_0, %E1_10... |
Supported PLC Memories
Area | Symbol | Digital Tag | Analog Tag |
CIO Area | CIO | CIO0.0 - CIO6143.15 | CIO0 - CIO6143 |
Work Area | W | W0.0 - W511.15 | W0 - W511 |
Holding Area | H | H0.0 - H511.15 | H0 - H511 |
AR Area | A | A0.0 - A959.15 | A0 - A959 |
T/C Status | TC | TC0 - TC4095 | - |
T/C PValue | PV | - | PV0 - PV4095 |
DM Area | D | D0.0 - D9999.15 | D0 - D9999 |
EM Area | EX_ (x:0~F) | E0_0.0 - EF_32767.15 | E0_0 - EF_32767 |
Communication Cable Wiring
This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX.
You can configure the cable and allocation pin number of RJ45 as shown below.
RJ45 Connector | RJ45 Jack |
Direct Cable: Host ↔︎ HUB
Cable | No | Color | Color | No | Cable |
| 1 | Orange/White | Orange/White | 1 |
|
2 | Orange | Orange | 2 | ||
3 | Green/White | Green/White | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/White | Blue/White | 5 | ||
6 | Green | Green | 6 | ||
7 | Brown/White | Brown/White | 7 | ||
8 | Brown | Brown | 8 |
Crossover Cable: Host ↔︎ Host
Cable | No | Color | Color | No | Cable |
| 1 | Orange/White | Green/White | 1 |
|
2 | Orange | Green | 2 | ||
3 | Green/White | Orange/White | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/White | Blue/White | 5 | ||
6 | Green | Orange | 6 | ||
7 | Brown/White | Brown/White | 7 | ||
8 | Brown | Brown | 8 |