14.1.1.1.2.10 Siemens S7

14.1.1.1.2.10 Siemens S7

This driver uses a standard Ethernet connection to communicate with Siemens S7 devices.

Communication Settings: Xpanel

I/O Device Configuration

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select Siemens S7 for Device Type.

 

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

 

 

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

See the Ethernet Communication Configuration section for more information.

Address and Supported Symbols

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.

Supported Symbols

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Process Inputs

I

I0.0 - I1023.7 (Max 65535.7)

I0 - I1023 (Max 65535)

Decimal

R/W

Process Outputs

Q

Q0.0 - Q1023.7 (Max 65535.7)

Q0 - Q1023 (Max 65535)

Decimal

R/W

Merkers

M

M0.0 - M4095.7 (Max 65535.7)

M0 - M4095 (Max 65535)

Decimal

R/W

DB

DB

DB0,0.0 - DB65535,65535.7

DB0,0 - DB65535,65535

Decimal

R/W

Counters

C

-

C0 - C65535

Decimal

R/W

Timer

T

-

T0 - T65535

Decimal

R/W

S7 1200/1500 notes:

  • Only global DBs can be accessed.

  • To access a DB memory area in S7 1200/1500, some additional settings in PLC software (TIA Portal) is required.

  • The optimized block access must be turned off.
    1) Select the DB in the left pane under “Program blocks” and press [Alt+Enter]. (Or in the contextual menu, select “Properties…”)
    2) Uncheck Optimized block access

  • The access level must be “full” and the “connection mechanism” must allow GET/PUT.
    1) Select the CPU project in the left pane and press [Alt+Enter]. (Or in the contextual menu, select “Properties…”.)
    2) Select “Full access” and check “Permit acess with PUT/GET …” as in the image below.

Communication Cable Wiring

This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.

RJ45 Connector

RJ45 Jack

Direct Cable: Host ↔︎ HUB

Cable

No.

Color

Color

No.

Cable

 

 

 

1

Orange/White

Orange/White

1

 

 

 

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host ↔︎ Host

Cable

No.

Color

Color

No.

Cable

 

 

 

1

Orange/White

Green/White

1

 

 

 

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8