This Driver supports the communication between the Xpanel and RF Temperature Measurement Sensor.

 

 Communication Setup: Xpanel

Create a new device

Select Tool -> I/O Device or click on the (blue star) icon from the toolbar. How to create an I/O Device is shown below.

I/O Device Name

To designate an I/O Device Name. This will be used in the Station Name and Tag Configuration of the Database.

Select a network type

 

Device Type: RF Temperature Measurement Sensor

If I/O Device Name designation is completed, the [Serial Communication Configuration] window appears as shown below.

Select RF Temperature Measurement Sensor as the Device Type, and set up the Comm. parameters exactly as the PLC configuration. Comm. parameters must be set up as shown below.

Parameter

Configuration

Baud Rate

Set to 115,200 (can vary depending on device setting).

Parity

None

Data Bit

8 Bits

Stop Bit

1 Bit

Comm. Type

RS232

Create a station

Go to the Station tab of the [Serial Communication Configuration] window. Station No. can be 1 to 15.

Station Name

To designate a Station Name. This will be used in the Tag Configuration of Database in Device Name field.

Station Type

Select Station Type Temp RF (no other option is allowed).

Network ID

N/A

Station No.

Station No. must be the same as PLC station number (1 - 15).

16Bit Data Swap

N/A

32Bit Data Swap

N/A

Using Checksum

N/A

Comm. Error Message Pop Up

With this feature on, communication error messages appear when the Xpanel detects Send/Receive errors. Error messages will disappear after 5 seconds.

 

 Address & Function Codes

How to designate a Comm. Address is shown below.

Address Format

 Address

Description

Data Type

In Bit Type

Access

T0

Sensor Temperature

INT32

-

Read Only