14.1.1.1.2.5 Mitsubishi MELSEC Ethernet

14.1.1.1.2.5 Mitsubishi MELSEC Ethernet

This driver uses a standard Ethernet connection to communicate with Mitsubishi MELSEC Ethernet devices such as FX5, Q/L.

Communication Settings: Xpanel

I/O Device Configuration

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select Mitsubishi MELSEC Ethernet for Device Type.

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

See the Ethernet Communication Configuration section for more information.

Address and Supported Symbols

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.

Supported Symbols

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Name

Symbol

Bit Range

Word Range

Address Number System

Access

Input

X

X0000 - X1757 (1777)

-

Octal

R

Output

Y

Y0000 - Y1757

-

Octal

R

Internal Relay

M

M0000 - M7659

-

Decimal

R/W

Latching Relay

L

L0000 - L7659

-

Decimal

R/W

Annunciator

F

F000 - F107

-

Decimal

R/W

Edge Relay

V

V0000 -V2029

-

Decimal

R/W

Link Relay

B

B000 - B0EF

-

Hexadecimal

R/W

Not supported for iQ-F FX5

Step Relay

S

S0000 - S4079

-

Decimal

R/W

Timer Contact

TS

TS000 - TS496

-

Decimal

R/W

Timer Coil

TC

TC000 - T496

-

Decimal

R/W

Retentive Timer Contact

SS

SS00 - SS00

-

Decimal

R/W

Retentive Timer Coil

SC

SC00 - SC00

-

Decimal

R/W

Counter Contact

CS

CS000 - CS240

-

Decimal

R/W

Counter Coil

CC

CC000 - CC240

-

Decimal

R/W

Link Special Relay

SB

SB000 - SB1EF

-

Hexadecimal

R/W

Special Relay

SM

SM0000 - SM9979

-

Decimal

R/W

Data Register

D

-

D0000 - D7999

Decimal

R/W

Link Register

W

-

W000 - W1FF

Hexadecimal

R/W

Timer CV

TN

-

TN000 - TN511

Decimal

R/W

Retentive Timer CV

SN

-

SN00 - SN15

Decimal

R/W

Counter CV

CN

-

CN000 - CN255

Decimal

R/W

Link Special Register

SW

-

SW000 - SW1FF

Hexadecimal

R/W

Special Register

SD

-

SD00000 - SD11999

Decimal

R/W

Communication Cable Wiring

This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.

RJ45 Connector

RJ45 Jack

Direct Cable: Host ↔︎ HUB

Cable

No.

Color

Color

No.

Cable

 

 

 

1

Orange/White

Orange/White

1

 

 

 

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host ↔︎ Host

Cable

No.

Color

Color

No.

Cable

 

 

 

1

Orange/White

Green/White

1

 

 

 

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Related content