ClosePort(PortNo.)

Closes the serial port.

Subroutine

EnableDriver(“DeviceName”, “StationName”, Enable/Disable)

Controls the selected station’s communication.

Function

GetCommStatus(“DeviceName”, “StationName”)

Checks the selected station’s communication status.

Function

OpenPort(PortNo., BaudRate, Parity, Data Bit, Stop Bit)

Opens the serial port.

Function

ReceiveByte(PortNo., Data)

Receives data with the selected port.

Function

SendByte(PortNo., Data)

Sends byte data with the selected port.

Function

SendString(PortNo., Data)

Sends string data with the selected port.

(blue star)

- EnableDriver() command only supports MODBUS RTU. (XpanelDesigner V2.52)

- GetCommStatus() command can only be used in the XpanelDesigner V2.52 or above.

PortNo., BaudRate, Parity, Stop Bit use predefined constants. Refer to the table shown below for the details.

Constant Name

Value

Usage

_COM232_

0

Uses COM1 port as RS232C mode.

_COM422_

1

Uses COM1 port as RS422 mode.

_COM485_

2

Uses COM1 port as RS485 mode.

_COMAUX_

3

Uses COM2 port as RS232C mode only.

_BPS300_

 

300 bps (Baudrate)

_BPS600_

 

600bps (Baudrate)

_BPS1200_

 

1200bps (Baudrate)

_BPS2400_

 

2400bps (Baudrate)

_BPS4800_

 

4800bps (Baudrate)

_BPS9600_

 

9600bps (Baudrate)

_BPS19200_

 

19200bps (Baudrate)

_BPS38400_

 

38400bps (Baudrate)

_BPS56000_

 

56000bps (Baudrate)

_BPS57600_

 

57600bps (Baudrate)

_BPS115200_

 

115200bps (Baudrate)

_BPS128000_

 

128000bps (Baudrate)

_BPS256000_

 

256000bps (Baudrate)

_PARITY_NONE_

 

No parity bit

_PARITY_EVEN_

 

Even parity

_PARITY_ODD_

 

Odd parity

_PARITY_MARK_

 

Mark parity

_PARITY_SPACE_

 

Space Parity

_STOPBIT_ONE_

 

1 STOP bit

_STOPBIT_TWO_

 

2 STOP bits

_STOPBIT_ONE5_

 

1.5 STOP bit

 

ClosePort

Closes the serial port.

Function

n=ClosePort(PortNo.)

Description

PortNo. (use predefined constant, _COMxxx_)

Closes the assigned serial port which was previously opened by the OpenPort() function.

If an error occurs during the port closing, the script will return 0. If the port closed successfully, the script would return a value other than 0.

Example

Closes COM1 port.

ClosePort(_COM485_);

 

EnableDriver

Controls the selected station’s communication.

Subroutine

EnableDriver(“DeviceName”, “StationName”, Enable/Disable)

Description

Controls the communication of the assigned StationName of the DeviceName.

You may Enable/Disable the communication with:

0: Disable

1: Enable

This function only supports MODBUS RTU at XpanelDesigner V2.52 and versions above.

Example

Enables the station “STATION” of the “MODBUS” device.

EnableDriver(“MODBUS”, “STATION”, 1);

GetCommStatus

Checks the selected station’s communication status.

Function

GetCommStatus(“DeviceName”, “StationName”)

Description

Returns the status of the assigned DeviceName ‘s StationName. If the communication is normal, the script will return 1. If there is an error with the communication, the script will return 0.

Example

Checks the communication status of the “PLC” device’s station: “STATION”.

CommStatus = GetCommStatus(“PLC”,”STATION”);

OpenPort

Opens the serial port.

Function

n=OpenPort(PortNo., BaudRate, Parity, Data Bit, Stop Bit)

Description

PortNo. (use predefined constant, _COMxxx_)

BaudRate (use predefined constant, _BPSxxx_)

Parity (use predefined constant, _PARITY_xxx_)

Data Bit (7 or 8)

Stop Bit (use predefined constant, _STOPBIT_xxx_)

This function opens the assigned serial port. You cannot use this function if the port has already been opened.

Once you opened the COM port with the script, it must be closed with ClosePort() function.

If an error occurs during the port opening, the script will return 0. If the port opened successfully, the script would return a value other than 0.

Example

Opens COM1 port with the following options; RS485, 19200bps, No Parity, Data Bit 8, Stop Bit 1.

OpenPort(_COM485_, _BPS19200_, _PARITY_NONE_, 8, _STOPBIT_ONE_);

ReceiveByte

Receives data with the selected port.

Function

ReceiveByte(PortNo., Data)

Description

PortNo. (use predefined constant, _COMxxx_)

Data (0~255)

This function is used when you wish to receive data with the COM port that was previously opened by the OpenPort() function.

Once you receive the data successfully, the Data (0~255) will be stored in the variable. If there is no received data until the timeout, the script will return 256.

The OpenPort() function must be used before the execution of the ReceiveByte() function.

Example

Receives byte data through the COM1 port which uses RS485 communication. Saves the received data at the variable ‘RxData’.

VAR RxData;

OpenPort(_COM485_, _BPS19200_, _PARITY_NONE_, 8, _STOPBIT_ONE_);

RxData = ReceiveByte(_COM485_, 1000);

If(RxData < 256)

{

}

……

SendByte

Sends byte data through the selected port.

Function

n=SendByte(PortNo., Data)

Description

PortNo. (use predefined constant, _COMxxx_)

Data (0~255)

This function is used when you wish to transmit data with the COM port that was previously opened by the OpenPort() function.

Data must be byte data in the range of 0(0x00) to 255(0xFF). If the data is greater than 255(0xFF), only the lower byte will be transmitted.

For example, if you assign Data with 0x1234, only 0x34 will be transmitted.

The OpenPort() function must be used before the execution of the SendByte() function.

If an error occurs during the data transmission, the script will return 0.

If the data transmitted successfully, the script would return a value other than 0.

Example

Transmits byte data “2” through COM1 port which uses RS485 communication.

SendByte(_COM485_, 2);

 

SendString

Sends string data through the selected port.

Function

SendString(PortNo., Data)

Description

PortNo. (use predefined constant, _COMxxx_)

Data (Enter the String Tag or “String”)

This function is used when you wish to transmit data with the COM port that was previously opened by the OpenPort() function.

The Data must be assigned with a string tag or string data. If you use the string data, it must be used with double quotation marks (“ “).

The OpenPort() function must be used before the execution of the SendString() function.

If an error occurs during the data transmission, the script will return 0.

If the data transmits successfully, the script will return a value other than 0.

Example

Transmits string data “TEXT” through COM1 port which uses RS485 communication.

SendString(_COM485_, “TEXT”);

 

 