Communication Setup: Xpanel

Create a new device

To configure the communication device of LSIS PLC, select [Tools] → [I/O Devices] or click the (blue star) icon in the main toolbar.

The ‘I/O Device Configuration’ dialog box will pop up. Click the [New Device] button.

I/O Device Name: Give a device name. The Device Name will be used in the Station Name and tag configuration of the database.

Select a device type

After selecting [Ok] in the previous step, the ‘Serial Communication Configuration’ dialog box will pop up as shown below.

Select ‘Fatek PLC Cnet’ from the ‘Device Type’ dropdown menu, and choose the appropriate communication parameters. Those parameters must be matched with the PLC. See the Communication Configuration section for more information.

Create a station

Move to the [Station] tab in the ‘Serial Communication Configuration’ dialog box and click [Add Station]. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel.

Station Name: Give a name to the PLC. This name will be used in the database window

accompanied by the Device Name.

Station Type: Choose the 'FATEK PLC' (no other type can be selected).

Network ID: This field has no meaning in this driver (ignored in runtime).

Station No.: Specify a decimal number between 0 and 126.

16Bit Data Swap: This field has no effect.

32Bit Data Swap: This field has no effect.

Using Checksum: This field has no effect. This communication driver always checks the box.

Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds.

See the Communication Configuration section for more information about the remaining parameters.

Communication Setting: FATEK PLC

1. Using CPU Loader Port

  • Run ‘WinProLadder’.

  • Select [PLC] - [On-Line] from the menu.

  • Select ‘RS232' in the ‘Connection Name’ field, and push [Auto Check] to open the ‘Connect Auto Check’ window.

  • Select the serial port on ‘Select Port No'.

  • Select PLC Type on ‘Select PLC Series’.

  • Select PLC side port on ‘Select Port’.

  • Press [OK] to do the connection auto check.

  • Now that the connection is finished, select [PLC] → [Setting] → [Station Number] to popup the ‘Station Number’ window.

  • After inputting the PLC station number, press [OK].

  • Select the port parameters on [PLC] → [Setting].

  • Select ‘Fatek Communication Protocol’ on Protocol.

  • After finishing the parameter settings, press the [OK] button.

  • If you use a serial loader port, check the Port0 parameter on [PLC] → [Setting].

Address Notation

Name

Symbol

Digital

Analog

16-Bit

32-Bit

Input discrete

X

X00-X9999

WX00-WX9984

DWX00-DWX9984

Output relay

Y

Y00-Y9999

WY00-WY9984

DWY00-DWY9984

Internal relay

M

M00-M9999

WM00-WM9984

DWM00-DWM9984

Step relay

S

S00-S9999

WS00-WS9984

DWS00-DWS9984

Timer discrete

T

T00-T9999

WT00-WT9984

DWT00-DWT9984

Counter discrete

C

C00-C9999

WC00-WC9984

DWC00-DWC9984

Timer register

TMR

 

RT00-RT9999

DRT00-DRT9999

Counter register

CTR

 

RC00-RC9999

DRC00-DRC9999

Data register

HR

 

R00-R65535

DR00-DR65535

Data register

DR

 

D00-D65535

DD00-DD65535

(1) Word tag is supported by 16-Bit only.

(2) Digital address is used only for digital tags.

(3) The 32-Bit address is used only for 32-Bit analog tags.