This Driver supports communication between Xpanel and the OMRON RFID Reader V680 Series.
This Driver is developed to support the V680 Command, Antenna 1 for 1:N Communication.
Communication Setup: Xpanel
Create a new Device
| To create a new device, select ‘Tools’ → ’I/O Devices’ or click the I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in the following picture: Select ‘OMRON RFID Reader’ as the ‘Device Type’, and set the communication parameters as shown below. Note: these settings reflect when pin 9 of the RFID DIP switch SW3 is ON (1:N Communication), and the rest of the pins are OFF. If you change the RFID switch settings, you must change the settings in XpanelDesigner to match. Baud Rate: 9600 Parity: Even Data Bit: 7 Stop Bit: 2 Bits RTS/CTS: OFF Comm. Type: RS232 See the Communication Configuration section for more information about the remaining parameters. |
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules: Station Name: Designate a name for the station. This will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Select ‘V680’ (this is the only available option). Network ID: N/A Station No: Enter the station number used by the communication module. The station number set within the RFID device configuration must match the number chosen here. See the Communication Configuration section for more information about the remaining parameters. |
Communication Configuration: RFID Reader (V680)
The table below summarizes the functionality of each of the switches shown above.
Name | Default Setting | Description | |
---|---|---|---|
SW1 | Controller number upper digit (0 to 9) | 0 | Controller No. 00 |
SW2 | Controller number lowe digit (0 to 9) | 0 | |
SW3, pin 1 | SW enable switch | OFF | DIP Switches enabled |
SW3, pin 2 | Reserved by system | OFF | (Not used) |
SW3, pin 3 | Baud rate setting 1 | OFF | Baud rate: 9600 bps |
SW3, pin 4 | Baud rate setting 2 | OFF | |
SW3, pin 5 | Data length | OFF | Data length: 7 bits |
SW3, pin 6 | Parity 1 | OFF | Parity: Even |
SW3, pin 7 | Parity 2 | OFF | |
SW3, pin 8 | Stop bit length | OFF | Stop bits: 2 |
SW3, pin 9 | Communications protocol | OFF | 1:1 |
SW3, pin 10 | Command system | OFF | V680 commands |
SW4, pin 1 | Test Mode switch setting 1 | OFF | Distance level measurement |
SW4, pin 2 | Test Mode switch setting 2 | OFF | |
SW4, pin 3 | Test Mode switch setting 3 | OFF | |
SW4, pin 4 | Antenna specification for test execution | OFF | Antenna 1 |
SW4, pin 5 | Write verification | OFF | With write verification |
SW4, pin 6 | Lower trigger execution setting | OFF | None |
SW4, pin 7 | Write protection function disable | OFF | Enabled |
SW4, pin 8 | V680-H01 Antenna connection setting | OFF | Connection to antennas other than the V680-H01 |
SW4, pin 9 | Run Mode setting | OFF | Command Execution Mode |
SW4, pin 10 | High-speed Data Transmission setting | OFF | Normal mode |
SW5 | Mode switch | OFF | Run Mode |
SW6 | Terminating resistance | OFF | No terminating resistance |
Detailed switch descriptions. Default settings are designated in bold.
SW1, SW2: Controller Number Switch
Ex) SW1: 1, SW2: 2 → Controller number = 12
SW3, PIN1: SW Enable Switch → OFF
OFF: DIP Switch Enabled.
ON: Internal Settings Enabled.
SW3, PIN2: Reserved → OFF
SW3, PIN3 and PIN4: Baud Rate. See the table below for more information:
SW3, pin 3 | SW3, pin 4 | Description |
---|---|---|
OFF | OFF | 9,600 bps |
ON | 19,200 bps | |
ON | OFF | 38,400 bps |
ON | 115,200 bps |
SW3, PIN5: Data Length
OFF: 7 bit
ON: 8 bit
SW3, PIN6 and PIN7: Parity. See the table below for more information:
SW3, pin 6 | SW3, pin 7 | Description |
---|---|---|
OFF | OFF | Even |
ON | None | |
ON | OFF | Odd |
ON | Even |
SW3, PIN8: Stop Bit
OFF: 2 Bits
ON: 1 Bit
SW3, PIN9: Communication Protocol → ON
OFF: 1:1
ON: 1:N
SW3, PIN10: Command System → OFF
OFF: V680 Command
ON: V600 Command
SW4, PIN1, PIN2, and PIN3: Maintenance mode switch settings → OFF, OFF, OFF
See the table below for more information:
SW4, pin 1 | SW4, pin 2 | SW4, pin 3 | Description |
---|---|---|---|
OFF | OFF | OFF | Distance Level Measurement Mode |
ON | Tag Communications Test Mode | ||
ON | OFF | Speed Level Measurement Mode, Read | |
ON | Speed Level Measurement Mode, Write | ||
ON | OFF | OFF | Noise Level Measurement Mode |
ON | OFF | Communications Success Rate Measurement Mode | |
ON | Host Communications Monitor Mode |
SW4, PIN4: Antenna Specification → OFF
OFF: Antenna 1ON: Antenna 2
SW4, PIN5: Write Verification → OFF
OFF: With write verification
ON: Without write verification
SW4, PIN6: Lower Trigger Execution → OFF
OFF: None
ON: Enable (on rising edge)
SW4, PIN7: Write protection function. → OFF
OFF: Enable
ON: Disable
SW4, PIN8: V680-H01 Antenna connection setting → OFF
OFF: Connection to antennas other than the V680-h01
ON: Allows connection of V680-h0 Antenna.
SW4, PIN9: Run mode → OFF
OFF: Command execution mode
ON: Self-execution mode
SW4, PIN10: High-speed data transmission setting → OFF
OFF: Normal mode
ON: High-speed mode
SW5: Mode switch setting → OFF
OFF: Run mode
ON: Maintenance Mode
SW6: Terminating resistance
OFF: Terminating resistance OFF
ON: Terminating resistance ON
Address Notation
Device | Unit | Description |
n:B0000 – n:B1999 | Byte | Tag Data area. Both Read and Write are allowed. |
n:W0000 – n:W1999 | Byte | Area to modify the RFID Tag value. Only Write is allowed. |
n:S0000 | Word | To display communication status. This area must be registered as INT16 or UINT16. |
Antenna designation is possible when “n:” is designated. Without designating “n:”, Attenna1 is designated (n is 1 or 2).
Ex) “2:B0000“ is byte B0000 of antenna 2. “1:W1000“ is word 1000 of antenna 1.
When the value of S0000 is 0, the status is normal. Otherwise, S0000 gives the error status. Refer to the error table below
Note: If the value is 255(FFh), this means Read Time Out (not listed below)
Type | Error Code | Name | Details |
---|---|---|---|
Host Communications Error | 10 | Parity error | Communications error between host device and ID Controller
|
11 | Framing error | ||
12 | Overrun error | ||
13 | FCS error | Incorrect calculation of FCS | |
14 | Command input error | Incorrect command format | |
15 | Execution status error |
| |
18 | Frame length error | The number of characters per command frame exceeds the specified value. | |
Tag Communications Error | 70 | Communications error | There is an error in communications between antennas and tags
|
71 | Mismatch error | Write has not been processed correctly | |
72 | Tag missing error | No Tag in communications area when read/write was executed | |
7A | Address designation error | An address outside the tag memory has been designated. | |
7C | Amplifier error |
| |
7D | Write protection error | A write-protected area was specified for a write command |
Wiring Diagram
RS-232C
|