Communication Setup: Inverter Setting (FC300, VLT2800)
Inverter Setting (FC300) | For normal communication, the following parameters must be set for the inverter. · Parameter 8-10 : FC profile [0] · Parameter 8-30 : FC MC [1] [1] Those parameters must be matched with the settings of the Xpanel. [2] The parameters of 8-10 and 8-30 must be set as the value shown above. If those parameters are set as other values, Xpanel cannot communicate with the inverter. |
Inverter Setting (VLT2800) | For normal communication, the following parameters must be set for the inverter.
[1] Those parameters (500 and 501) must be matched with the settings of the Xpanel. [2] The parameter of 502 must be set as the value shown above. If this parameter is set as another value, Xpanel cannot communicate with the inverter. |
Communication Setup: Xpanel
Create a new device | For creating a new device go to [Tools] - [I/O Devices] or click the The following picture demonstrates the first step for creating a new device. I/O Device Name: Give a device name. This name will be used in the Tag configuration window of the database accompanied by the Station Name. |
Select a device type | After selecting [OK] on the previous step, the ‘Serial Communication Configuration’ dialog box will be popped up as shown in the following picture. In this window, select the ‘Device Type’ as ‘DANFOSS VLT AutomationDrive FC-300’ and configure the proper serial communication parameters. See the Communication Configuration section for more information.
|
Create a station | Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel. Each field can be configured as followed: Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the ‘Device Name’. Station Type: Choose the ‘FC-300’ (no other type can be selected). Network ID: This field has no effect. Station No.: Specify a number between 0 and 9. 16Bits Data Swap: This field has no effect. 32Bits Data Swap: This field has no effect. String Data Swap: This field has no effect. Using CheckSum: This field has no effect. Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. See the Communication Configuration section for more information about the remaining parameters. |
Address Notation
The address of a tag in Xpanel has the following format:
Tag Type | Format | Example |
Analog | [Symbol][Decimal Number] | P023 |
Digital | [Symbol][Decimal Number][.][Hexadecimal Number] | P000.F |
Symbol | Address | Description | Access |
P | 0001 - 1760 | Parameter Area The address of each tag can be induced from the parameter number of FC 300 or VLT 2800. For example, to monitor the ‘16-17 Speed [RPM]' of FC 300, the address should be designated with 'P1617’. For more parameters, please refer to the ‘How to Program’ section of the “FC 300 Design Guide”. The value written to this address will be transferred to the FC 300 or VLT 2800 directly. That means parameters of the inverter can be modified by writing the desired value to this address. The new value can be stored to not only RAM, but also to EEPROM of FC 300. For storing a set value to the EEPROM, the C002 point must have a non-zero value. | R/W |
C | 000 | Control Code 1 word-sized control data. Each bit has its own control meaning which is shown in the following ‘Control Code’ table. To control FC 300 or VLT 2800, write a value of the combination of the table. Ensure that the reference (C001) is set as the desired value before issuing this control code. | W |
001 | Reference This point is a signed word data (-32767 - +32767), and the range of data corresponds to -200% to +200% of reference. For example, the value of 16384 represents 100% of reference. This reference value must be set before the actual control by control code (C000). | ||
002 | EEPROM Writing If this is non-zero, the value written to the parameter area (Pnnnn) will be saved to the EEPROM as well as RAM of FC 300 or VLT 2800. Otherwise, the set value will be stored only in RAM. Ensure that this point is set as the desired value before parameter writing. |
The addresses above can be used in both analog and digital tags.
For more information on each point, please refer to the ‘FC 300 Design Guide’.
[C000 : Control Code for FC 300]
Bit No. | Bit Value = 0 | Bit Value = 1 |
00 | Reference value | External selection lsb |
01 | Reference value | External selection msb |
02 | DC brake | Ramp |
03 | Coasting | No coasting |
04 | Quick stop | Ramp |
05 | Freeze output | Use ramp |
06 | Ramp stop | Start |
07 | No function | Reset |
08 | No function | Jog |
09 | Ramp 1 | Ramp 2 |
10 | Data not valid | Data valid |
11 | Relay 01 open | Relay 01 active |
12 | Relay 02 open | Relay 02 active |
13 | Parameter set-up | Selection lsb |
14 | Parameter set-up | Selection msb |
15 | No function | Reverse |
For more information on each bit, refer to the ‘Control Word According to FC Profile (CTW)’ section of the ‘FC 300 Design Guide’.
[C000 : Control Code for VLT2800]
Bit No. | Bit Value = 0 | Bit Value = 1 |
00 |
| Preset reference lsb |
01 |
| Preset reference msb |
02 | DC brake |
|
03 | Coasting stop |
|
04 | Quick stop |
|
05 | Freeze output frequency |
|
06 | Ramp stop | Start |
07 |
| Reset |
08 |
| Jog |
09 | Ramp 1 | Ramp 2 |
10 | Data not valid | Data valid |
11 |
| Relay 01 activated |
12 |
| Digital output terminal 46 activated |
13 | Selection setup, lsb |
|
14 | Selection setup, msb |
|
15 |
| Reverse |
For more information on each bit, refer to the ‘Control Word According to FC Profile (CTW)’ section of the ‘FC 2800 Design Guide’.
Example: Monitors the frequency data
Make an analog tag for frequency data. The address can be induced from parameter 16-13. Designate ‘P1613’ as the address of the new analog tag.
Setup the scale factor of the analog tag if needed. The ‘Conversion index’ of parameter 16-13 is -1. Configure the scaling factor of the tag in the database as 0.1.
The ‘Conversion index’ and other useful information of each parameter can be found on the ‘Parameter Lists’ section of the ‘FC 300 Design Guide’.
Example: Changes the ‘speed PID lowpass filter time’
Make two analog tags. One tag is for EEPROM storage control and the other tag is for the parameter. The address of the parameter tag can be induced from parameter 07-06. Designate ‘P0706’ as the address of the new analog tag.
2. Setup the scale factor of the analog tag. In this example, the value of 0.1 was designated as the scale factor. The ‘Conversion index' of the parameter 07-06 is -4. This index is based on the unit of seconds. For convenience, we can use the unit of milliseconds, such that the index can be thought of as the value of -1.
3. The parameter of FC 300 can be modified by changing the tag. If needed, the EEPROM storing option can be arranged before writing a new parameter value.
The following image shows an example of how to change a parameter:
Example: Start Controls
Make two analog tags for control. One tag is for a reference value (C001, INT16) and the other tag is for a control word (C000, UINT16).
2. To control the FC 300, write the desired reference value to the ‘Reference’ point, C001, first. Then, write a control value to the ‘Control' point. For example, write the value of 0x047F for issuing a start command.
The following picture shows an example of a command expression for control, starting with 100%.
Communication Cable Wiring
Shielded twisted pair cable must be used for P-N pair.
Ensure that the shielded cable is connected to the COM terminal (61) of FC 300.