This driver supports communication with MELSEC-FX series PLCs through an RS-232C/422A port.
This driver uses the dedicated protocol for the FX series and uses control protocol format 1.
Communication Setup: Xpanel
Create a new device | To create a new device, select ‘Tools’ → ’I/O Devices’ or click the icon in the toolbar. The following picture shows the first step in creating a new device: I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in the following picture: In this window, set the ‘Device Type’ to ‘MITSUBISHI Melsec FX’ and configure the remaining serial communication parameters. Ensure that these parameters are matched with the PLC configuration. |
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules: Station Name: Give a name to the PLC. This name will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Choose the type of connected PLC (“FX“ is the only available option). Network ID: N/A Station No: Specify a decimal number between 0 and 15. This number must be matched with the number in the special data register D8121 of the FX PLC. 16-Bit Data Swap: N/A 32-Bit Data Swap: N/A String Data Swap: N/A Using Checksum: This field has no effect. This communication driver always uses a checksum. Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. |
Communication Setup: MELSEC FX PLC
Configuration on the PLC side is performed using the ‘GX Developer’ application.
For normal communication with Xpanel, the following parameters must be set as shown:
Protocol | Dedicated Protocol |
Format | Protocol Format 1 |
Sum Check | Enable |
Address Notation
Memory | CPU | Format | Bit/Word | |||
FX0n | FX,FX2c | FX2n | ||||
Input | X | X0000-X0177 | X0000-X0337 | X0000-X0267 | Octal | Bit |
Output | Y | Y0000-Y0177 | Y0000-Y0337 | Y0000-Y0267 | Octal | Bit |
Aux Relay | M | M0000-M0511 | M0000-M1535 | M0000-M3071 | Decimal | Bit |
Special Relay | M | M8000-M8254 | M8000-M8255 | M8000-M8255 | Decimal | Bit |
Status Relay | S | S0000-S0127 | S0000-S0999 | S0000-S0999 | Decimal | Bit |
Data Register | D | D0000-D8255 | D0000-D8255 | D0000-D8255 | Decimal | Word |
Timer | TN | TN000-TN063 | TN000-TN255 | TN000-TN255 | Decimal | Word |
Counter | CN | CN000-CN254 | CN000-CN255 | CN000-CN255 | Decimal | Word |
Wiring Diagram
RS-232C |
|
RS-422 | |
RS-485 |