This driver supports communication with a CIMON PLC through the RS-232C or RS-422A HMI Protocol. The following PLC modules (options) support this HMI Protocol.
CP/XP Series
BP Series
PLC-S Series
MP Series
Communication Setup: Xpanel
Create a new device | To create a new device, select ‘Tools’ → ‘I/O Devices’ or click the I/O Device Name: Assign a device name. This name will be used in the tag configuration window of the database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in following picture: In this window, select ‘CIMON-PLC HMI’ as the device type and configure the remaining serial communication parameters. Ensure that these parameters match with the PLC configuration. |
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules. Station Name: Give a name to the PLC. This name will be used to assign device tag names in the database window, accompanied by the ‘Device Name’. Station Type: Choose the type of the connected PLC. Options include “CP/XP Series”, “BP Series“, “PLCS Series“, and “MP Series“. Network ID: N/A Station No: Specify a decimal number between 0 and 31. 16bits Data Swap: N/A 32bits Data Swap: N/A Using Checksum: N/A Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. |
Communication Setup: PLC
Communication Module | If one of the following special function modules is used for an Xpanel connection, the module properties should be configured in CICON as shown in the following picture.
‘Protocol’ must be set to ‘HMI Protocol’. Ensure that the other communication parameters are matched with XpanelDesigner. |
CPU Embedded Port | If a built-in CPU port is used to connect to an Xpanel, the PLC port parameters must be configured within CICON, as shown in the following picture. Note that the channel number and type of serial connection (232, 422, or 485) may vary depending on the selected PLC model. This type of communication is supported by the following models:
|
Supported PLC Memory Addresses
Area | Symbol | Analog tag | Digital Tag | Remark |
External Input | X | X0000 – X5110 | X0000 – X511F |
|
External Output | Y | Y0000 – Y5110 | Y0000 – Y511F |
|
Internal Relay | M | M0000 - M9990 | M0000 - M999F |
|
Internal Relay | L | L0000 – L9990 | L0000 – L999F |
|
Latch Relay | K | K0000 – K9990 | K0000 – K999F |
|
Flags | F | F0000 – F1270 | F0000 – F127F | Read Only |
Timer Output | T | Not supported | T0000 – T4095 |
|
Timer PV | TC | TC0000 – TC4095 | Not supported |
|
Timer SV | TS | TS0000 – TS4095 | Not supported |
|
Counter Output | C | Not supported | C0000 – C4095 |
|
Counter PV | CC | CC0000 – CC4095 | Not supported |
|
Counter SV | CS | CS0000 – CS4095 | Not supported |
|
Data Memory | D | D00000 – D31999 | Not supported |
|
Wiring Diagrams
RS-232C
CM1-SC01A,SC02A CM2-BPnnMxx-T | |
CM1-CP4C: Option Port | |
CM2-BP16Mxx-R |
RS-422A
CM1-SC01A,SC02A | |
CM1-CP4C: Option Port | |
CM2-BP16Mxx-S | |
CM2-BPnnMxx-U |