(1) Alarm Type
Select the analog alarm condition among three types.
Item | Description |
Value | The alarm occurs according to the analog tag value’s boundary value. |
Deviation | The alarm occurs according to the assigned target value and the difference between the tag value and target value. |
ROC | The alarm occurs according to the rate of change in tag value. |
(2) Alarm Configuration
Item | Description |
Enable | Enable or disable the alarm operation. |
Hysteresis | When the analog value changes around the setting value, it may cause the repetitive occurrence of the alarm. To prevent this situation, assign the sensitivity of the alarm. The alarm will occur only when the value exceeds the setting value and the hysteresis value. Also, the alarm will be cleared only when the value is less than the hysteresis value subtracted from the setting value. |
Delay-Time | You may assign the delay time of the alarm in seconds. If the alarm is turned OFF in the delay time, it is not assumed as an alarm. You can assign from 0 to 99999.9 seconds. |
Level | Assign the alarm level. You can assign from 1 to 15 grade. (In case of CIMON-SCADA Version lower than 3.04, 1 to 8 grade) In the [Alarm Configuration] window, you can output the specific alarm according to the level. |
Zone | Assign the location of the digital alarm. You can assign the alarm zone from A to P. In the [Alarm Configuration] window, you can output the specific alarm according to the alarm zone. |
The tag value has changed from the Lo area to normal area as shown below. However, since the value did not exceed the hysteresis value, the alarm state does not change. In the figure shown below, the tag value has changed from the Hi area to the normal area. Since the value exceeded the hysteresis value, the Hi alarm will be cleared. |
(3) Value Alarm
Assigning the boundary value as a criterion, the alarm occurs when the measured value is greater or less than the boundary value.
...
HiHi
Item | Description | |
HiHi | An alarm which occurs when the measured value is more than or exceeds the Hi-Hi boundary value. | |
Alarm | HiHi | A fiducial value of HiHi alarm. HiHi alarm occurs when the tag value is more than or exceeds the boundary value. |
Included | When this option is selected, it indicates that the HiHi alarm will occur when the tag value is same as the boundary value or more. If the option is deselected, it indicates that the HiHi alarm will occur when the tag value exceeds the boundary value. | |
On Label | Enter the label which will appear on the HiHi alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
Hi
Item | Description | |
Hi | An alarm which occurs when the measured value is more than or exceeds the Hi boundary value. | |
Alarm | Hi | A fiducial value of Hi alarm. Hi alarm occurs when the tag value is more than or exceeds the boundary value. |
Included | When this option is selected, it indicates that the Hi alarm will occur when the tag value is same as the boundary value or more. If the option is deselected, it indicates that the Hi alarm will occur when the tag value exceeds the boundary value. | |
On Label | Enter the label which will appear on the Hi alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
Lo
Item | Description | |
Lo | An alarm which occurs when the measured value is less than or under the Lo boundary value. | |
Alarm | Lo | A fiducial value of Lo alarm. Lo alarm occurs when the tag value is less than or under the boundary value. |
Included | When this option is selected, it indicates that the Lo alarm will occur when the tag value is same or less than the boundary value. If the option is deselected, it indicates that the Lo alarm will occur when the tag value is under the boundary value. | |
On Label | Enter the label which will appear on the Lo alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
LoLo
Item | Description | |
LoLo | An alarm which occurs when the measured value is less than or under the LoLo boundary value | |
Alarm | LoLo | A fiducial value of LoLo alarm. Lo alarm occurs when the tag value is less than or under the boundary value. |
Included | When this option is selected, it indicates that the LoLo alarm will occur when the tag value is same or less than the boundary value. If the option is deselected, it indicates that the LoLo alarm will occur when the tag value is under the boundary value. | |
On Label | Enter the label which will appear on the LoLo alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
(4) Deviation Alarm
According to the difference between the tag value and target value, the alarm occurs.
...
Major Dev
Item | Description | |
Major Dev | An alarm which occurs when the measured value exceeds the range of major deviation value. | |
Alarm | Target | Assign the value which will be the criterion of the Deviation Alarm. This value is used as the common target value of the Major and Minor Dev Alarm. |
Major Dev | Assign the value to turn on the Major Dev alarm. When the difference between the tag and target value is greater than the value assigned to Major Dev, the alarm will occur. The value assigned to the ‘Major Dev’ must be greater than the value assigned to the ‘Minor Dev’. | |
On Label | Enter the label which will appear on the Major Dev alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
Minor Dev
Item | Description | |
Minor Dev | An alarm which occurs when the measured value exceeds the range of minor deviation value. | |
Alarm | Target | Assign the value which will be the criterion of the Deviation Alarm. This value is used as the common target value of the Major and Minor Dev Alarm. |
Major Dev | Assign the value to turn on the Minor Dev alarm. When the difference between the tag and target value is less than the value assigned to Major Dev, the alarm will occur. The value assigned to the ‘Minor Dev’ must be less than the value assigned to the ‘Major Dev’. | |
On Label | Enter the label which will appear on the Minor Dev alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
(5) ROC Alarm
According to the rate of change in the measured value, the alarm occurs if the rate exceeds the assigned value difference.
...
Item | Description | |
Alarm | ROC | Assign the ROC value which will generate the alarm. If the difference between the previous data and the newly acquired data is greater than the rate, the alarm will occur. |
On Label | Enter the label which will appear on the ROC alarm. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
On Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. ※ Please refer to the ‘Comment Table’ manual for the more information. |
(6) Common Setup
Item | Description | |
Alarm Off | Ack Label | Enter the label which will appear when the alarm is acknowledged. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. |
Off Label | Enter the label which will appear when the alarm is cleared. You can check the label at the ‘Alarm Description’ option in [Format] tab of [Alarm Summary] window. | |
Off Action | You can assign an action when the alarm occurs. | |
Use Comment | When you select the option, […] button is activated, and you may use the comment table. | |
Alarm ACK | All Alarm Ack Act Enable | When you select the option, the assigned action is executed at the all alarms are acknowledged by the command ‘AlarmAckALL’, which acknowledges the entire tag with ‘Assign as Alarm Tag’ option. |
Action | Enter a command expression which will be executed when the alarm tag is acknowledged. To execute the command expression entered here, the ‘Define Tag action’ option in the [General] tab must be selected beforehand. |
(7) Tag Variables
Followings are the tag variables related to the analog alarm. The tag variables are used as ‘Tag Name:Tag Variable’.
Tag Variables | Description | R/W |
ALARMTYPE | Displays the alarm type assigned to the analog tag. (1: Value, 2: Deviation, 3: ROC) | R |
ALARMENABLE | Displays the alarm state. When the CimonX is executed, you may generate (1) or clear the alarm (0). | R/W |
HYSTERESIS | Displays the hysteresis value of the corresponding alarm. | R/W |
ALARMHIHI | Displays the HiHi boundary value of the alarm. | R/W |
ALARMHI | Displays the Hi boundary value of the alarm. | R/W |
ALARMLO | Displays the Lo boundary value of the alarm. | R/W |
ALARMLOLO | Displays the LoLo boundary value of the alarm. | R/W |
INALARM1 | Displays the ‘On Label’ of the following analog alarms. l Value - HiHi l Deviation – Major Dev l ROC | R/W |
INALARM2 | Displays the ‘On Label’ of the following analog alarms. l Value – Hi l Deviation – Minor Dev | R/W |
INALARM3 | Displays the ‘On Label’ of the Lo alarm. | R/W |
INALARM4 | Displays the ‘On Label’ of the LoLo alarm. | R/W |
ALARMTARGET | Displays the value assigned to the target value. | R/W |
ALARMMAJOR | Displays the value assigned to the Major Dev. | R/W |
ALARMMINOR | Displays the value assigned to the Minor Dev. | R/W |
ALARMROC | Displays the value assigned to the ROC. | R/W |
ACKLABEL | Displays the On or Off Label according to the alarm state. | R |
ALARMACK | Displays the alarm acknowledge state. | R/W |
ALARMVALUE | Displays the tag value on the moment of alarm state change. | R |