This driver uses a standard Ethernet connection to communicate with EtherNet/IP devices.

Communication Settings: Xpanel

I/O Device Configuration

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select Allen-Bradley EtherNet/IP for Device Type.

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

See the Ethernet Communication Configuration section for more information.

Communication Settings: PLC

ControlLogix/CompactLogix

  • Open RSLogix/Studio 5000.

  • Click [Controller Tags] → [New Tag…].

  • Setup Tag Name and Data Type in [New Tag…].

  • Write any tag names.

  • The next steps are for PCCC communication. If you would like to use tag-based addressing, please skip the next three steps and resume with setting an IP address.

    • Click [Logic] → [Map PLC/SLC Messages].

    • Make mapping File Number and Name in PLC2,3,5 / SLC Mapping.

    • File Number is set according to the address table.

  • Set up an IP address at RSLogix/Studio 5000 or RSLinx.

    Image Modified

    Image Modified

MicroLogix

  • Run RSLogix 500.

  • Select [Comms] → [Upload…] from the menu, and upload a project.

    Image RemovedImage Added

  • Double-click on [Channel Configuration] from the project window to open the ‘Channel Configuration’ window.

  • Go to the [Chan.1 - System] tab in the ‘Channel Configuration’ window.

    Image RemovedImage Added

  • Configure and save the IP Address, Subnet Mask, and Gateway Address.

  • Select [Comms] → [Download..], and download the setting to PLC.

Micro800

  • Open Connected Components Workbench.

  • Click [Global Variables] in the Project Tree → [New…].

  • Setup Tag Name and Data Type.

    Image Added

  • Set up an IP address at Connected Components Workbench. Double-click the CPU in the Project Tree, and enter the IP information within the Ethernet branch of the Controller.

    Image Added

Address and Function Codes

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

...

  • These CPUs are tag-based and can have their data registers addressed verbatim (i.e., there is a data register named DIG1 in the Micro850 PLC, then the IO address in Canvas will be DIG1).

ControlLogix/CompactLogix

  • PCCC Mapping

Address Structure: [Symbol][File No.]:[Element No.]/[Bit No.]

...

Address Structure: [Symbol][File No.]:[Element No.]/[Bit No.]

...

Name

...

Symbol

...

Digital

...

Analog

...

BOOL (BOOL)

...

B

...

B0:0/0 - B999:999/31

...

B0:0 - B999:999

...

INT (WORD)

...

N

...

N0:0/0 - N999:999/15

...

N0:0 - N999:999

...

REAL (FLOAT)

...

F

...

F0:0/0 - F999:999/31

...

Supported Symbols

MicroLogix

Symbol

Bit Range

Word Range

Name

O

O:0.0/0 – O:30.255/15

O:0.0 – O:30.255

Output

I

I:0.0/0 – I:30.255/15

I:0.0 – I:30.255

Input

S

S:0/0 – S:163/15

S:0 – S:163

Status

B

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

Binary

N

N7:0/0 – N7:255/15

N9:0/0 – N255:255/15

N7:0 – N7:255

N9:0 – N255:255

Integer

F

 

F8:0 – F255:255

  • Registration is allowed in Float only.

Float

L

 

L9:0 – L255:255

  • Registration is allowed in UINT32, INT32 only.

Long

ST

 

ST9:0 – ST255:255

String

T

T4:0.0/0 – T4:255.2/15

T9:0.0/0 – T255:255.2/15

 Txx:nn.0/15 = Enable(EN)

Txx:nn.0/14 = Timer Timing(TT)

Txx:nn.0/13 = Done(DN)

T4:0.0 – T4:255.2

T9:0.0 – T255:255.2

Txx:nn.1 = Preset Value(PRE)

Txx:nn.2 = Accumulated Value(ACC)

Timer

C

C5:0.0/0 – C5:255.2/15

C9:0.0/0 – C255:255.2/15

 Cxx:nn.0/15 = Count up enable(CU)

Cxx:nn.0/14 = Count down enable(CD)

Cxx:nn.0/13 = Done(DN)

Cxx:nn.0/12 = Overflow(OV)

Cxx:nn.0/11 = Underflowt(UN)

Cxx:nn.0/10 = Update Accumulator(UA)

C5:0.0 – C5:255.2

C9:0.0 – C255:255.2

Cxx:nn.1 = Preset (PRE)

Cxx:nn.2 = Accumulated Value(ACC)

Counter

R

R6:0.0/0 – C6:255.2/15

R9:0.0/0 – R255:255.2/15

 Rxx:nn.0/15 = Enable(EN)

Rxx:nn.0/14 =Update Enable(EU)

Rxx:nn.0/13 = Done(DN)

Rxx:nn.0/12 = Stack Empty(EM)

Rxx:nn.0/11 = Error(ER)

Rxx:nn.0/10 = Upload(UL)

Rxx:nn.0/9 = Inhibit(IN)

Rxx:nn.0/8 = Found(FD)

R6:0.0 – R6:255.2

R9:0.0 – R255:255.2

 Rxx:nn.1 = Length value

Rxx:nn.2 = position value

Control

Communication Cable Wiring

This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.

...