This driver uses a standard Ethernet connection to communicate with EtherNet/IP devices.

Communication Settings: Xpanel

I/O Device Configuration

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select Allen-Bradley EtherNet/IP for Device Type.

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

See the Ethernet Communication Configuration section for more information.

Communication Settings: PLC

ControlLogix/CompactLogix

MicroLogix

Micro800

Address and Function Codes

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.

Address Format

ControlLogix/CompactLogix/Micro800

ControlLogix/CompactLogix

Address Structure: [Symbol][File No.]:[Element No.]/[Bit No.]

Name

Symbol

Digital

Analog

BOOL (BOOL)

B

B0:0/0 - B999:999/31

B0:0 - B999:999

INT (WORD)

N

N0:0/0 - N999:999/15

N0:0 - N999:999

REAL (FLOAT)

F

F0:0/0 - F999:999/31

F0:0 - F999:999

MicroLogix

Address Structure: [Symbol][File No.]:[Element No.]/[Bit No.]

Supported Symbols

MicroLogix

Symbol

Bit Range

Word Range

Name

O

O:0.0/0 – O:30.255/15

O:0.0 – O:30.255

Output

I

I:0.0/0 – I:30.255/15

I:0.0 – I:30.255

Input

S

S:0/0 – S:163/15

S:0 – S:163

Status

B

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

Binary

N

N7:0/0 – N7:255/15

N9:0/0 – N255:255/15

N7:0 – N7:255

N9:0 – N255:255

Integer

F

 

F8:0 – F255:255

  • Registration is allowed in Float only.

Float

L

 

L9:0 – L255:255

  • Registration is allowed in UINT32, INT32 only.

Long

ST

 

ST9:0 – ST255:255

String

T

T4:0.0/0 – T4:255.2/15

T9:0.0/0 – T255:255.2/15

 Txx:nn.0/15 = Enable(EN)

Txx:nn.0/14 = Timer Timing(TT)

Txx:nn.0/13 = Done(DN)

T4:0.0 – T4:255.2

T9:0.0 – T255:255.2

Txx:nn.1 = Preset Value(PRE)

Txx:nn.2 = Accumulated Value(ACC)

Timer

C

C5:0.0/0 – C5:255.2/15

C9:0.0/0 – C255:255.2/15

 Cxx:nn.0/15 = Count up enable(CU)

Cxx:nn.0/14 = Count down enable(CD)

Cxx:nn.0/13 = Done(DN)

Cxx:nn.0/12 = Overflow(OV)

Cxx:nn.0/11 = Underflowt(UN)

Cxx:nn.0/10 = Update Accumulator(UA)

C5:0.0 – C5:255.2

C9:0.0 – C255:255.2

Cxx:nn.1 = Preset (PRE)

Cxx:nn.2 = Accumulated Value(ACC)

Counter

R

R6:0.0/0 – C6:255.2/15

R9:0.0/0 – R255:255.2/15

 Rxx:nn.0/15 = Enable(EN)

Rxx:nn.0/14 =Update Enable(EU)

Rxx:nn.0/13 = Done(DN)

Rxx:nn.0/12 = Stack Empty(EM)

Rxx:nn.0/11 = Error(ER)

Rxx:nn.0/10 = Upload(UL)

Rxx:nn.0/9 = Inhibit(IN)

Rxx:nn.0/8 = Found(FD)

R6:0.0 – R6:255.2

R9:0.0 – R255:255.2

 Rxx:nn.1 = Length value

Rxx:nn.2 = position value

Control

Communication Cable Wiring

This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.

RJ45 Connector

RJ45 Jack

Direct Cable: Host ↔︎ HUB

Cable

No.

Color

Color

No.

Cable

1

Orange/White

Orange/White

1

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host ↔︎ Host

Cable

No.

Color

Color

No.

Cable

1

Orange/White

Green/White

1

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8