Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Current »

(1) Editing the variable table in CICON

Create a PLC project in the CICON software and go to [Tools] -> [Variable Window]. The variable editor will appear. You can input the information for each device address. Contents are generated by saving the PLC project.

※ Please refer to the CICON help for more information about the variable editor.

(2) Loading the variable table

Press [Tools] -> [Loading CICON Variable Table Info.] in XpanelDesigner and the file browser will appear. You can browse for the variable table file (*.var file format) which is edited in CICON versions 6.00 and below.

Select the variable table file and press [Open] to prompt the ‘I/O Device Configuration’ dialog box. When the I/O device settings are not saved in XpanelDesigner, add a new device by pressing the [New Device] button.

Item

Description

Edit

Modifies the selected I/O device.

New Device

Adds a new I/O device. The manufacturer must be selected as ‘ATIVA-PLC’.

Delete

Deletes the selected I/O device from the project.

Select

Applies the contents of the variable table to the selected I/O device.

The following message will appear when you select the station name. You can convert variables of the CICON project into tags of XpanelDesigner.

A group tag is created with an I/O device name at the top-level of the database. Another group tag with station name is created under the ‘I/O device’ group. Each variable is changed to the tags according to the device information.

The table below explains the contents of the conversion.

CICON

XpanelDesigner

Variable Name

Tag Name

Description

Description

Device

I/O Address

Bit

Digital Tag (Initial value: 0)

Word

Analog Tag (Initial value: 0)

  • No labels