Performance Specifications(CM1 TC)
Items | CM1-TC04A | ||||
Available Thermocouple | Type K, J, E, T, B, R, S, N | ||||
Digital Conversion | Digitally converted value: 0–16000 (-8000–8000) Converted temperature value: (Range of measured temp.X10) | ||||
Range of Temperature | Type | Code | Range of Measured Temperature (℃) | Range of Measured Temperature (μV) | |
K | KS C162 | -200.0–1200.0 | -5891–48828 | ||
J | -200.0–800.0 | -7890–45498 | |||
E | -200.0–600.0 | -8824–45085 | |||
T | -200.0–400.0 | -5602–20869 | |||
B | 400.0–1800.0 | 786–13585 | |||
R | 0.0–1750.0 | 0–21006 | |||
S | 0.0–1750.0 | 0–18612 | |||
N | -200.0–1250.0 | -3990–43846 | |||
RJC | Automatic | ||||
Detecting the Breaking of Wires | By channel | ||||
Accuracy | ±[Full Scale] x 0.3% + 1°C (RJC Error)] | ||||
Max. Converted Rate | 50 ms/1 Channel | ||||
No. of Input Channels | 4 channels/module | ||||
Insulation | Between input terminal and PLC: Photocouple, | ||||
Connection Terminal | 18 points Terminal Block | ||||
Internal Current (mA) | +5 V | 60 | |||
+15 V | 30 | ||||
-15 V | 10 |