Performance Specifications(CM1 DataLogger)
Item | Specification | |
Processing System | Multi-task (high speed, multiprocessing) | |
(*) Memory Capacity | 4 GB (2 GB for logging data) | |
Function Setting | Using CICON software (PLC loader program) | |
App Upgrade Feature | Application downgrade/upgrade feature is supported | |
CM1-CPU | Connection Method | Connection with RS-232C port or USB at CPU module |
Configuration | Network setting, logging type, logging cycle, data list, Log file ID (*) | |
Monitoring | The number of clients, communication status, logged data transmission status, progress of data logging, CPU status, memory consumption (%), memory overflow (automatic dump, deletion) status, error information | |
Communication Function | Communication Standard | Ethernet 10/100 Mbps or 1 Gbps |
Protocol | TCP, CIMON HMI Ethernet Protocol | |
Access limitation | Simultaneous connections of up to 5 clients (Up to 3 clients can simultaneously access when using FTP feature) | |
Comm. Cable | Over CAT.5 STP (Shielded Twisted pair) cable | |
Maximum Distance | Maximum 100 m for preliminary physical connection with the network device (host system, hub, router, etc.) | |
Logging Function | Logging Type | Event Sampling, trigger monitoring (*) |
Range of Cycle | 1 – 327,67 (x L ms) L (*) = Time interval scale (1, 10, 100) The value is fixed at L = 10 below V2.0 | |
Range of Deadband | 0 ~ 65535(*) The value is fixed at ‘0’ in under V2.0. | |
Logging Device Type | X, Y, M, L, K, F, T, TC, TS, C, CC, CS, S, D, Z, R Device in PLC CPU | |
Data Type | Bit, Byte, Word, DWord, DDWord | |
Data Storage | Non-volatile memory (ROM) storage (Does not require a battery) | |
Data Capacity | 24 bytes for saving in a single device type | |
Data Managing | Storage Method | Event sampling: Saving data by date/hour Trigger monitoring (*): Saving data by file ID (Including time information) |
Delete Method | Automatic delete: The oldest data is deleted when memory is at capacity (Overflown) Manual delete: All logged data, (*) event sampling log data, (*) trigger monitoring log data | |
Compatible Host System | SCADA V3.90 and above version including ‘Historian’ feature Recommended system requirements: 64-bit version of Windows, 8GB RAM | |
Range of Time Synchronization Frequency | 1–32767 (x10 sec) | |
Error Display | LED, Display error code (LG02G configuration/monitoring window in CICON) | |
Comm. Status Display | LED, Display error code (LG02G configuration/monitoring window in CICON) | |
Number of Input/Output Points | 16 points (input 16 points/output 16 points) | |
Current Consumption | 136 mA | |
Weight | 113.5 g |