CM1-AD04VI has 4 channels Analog input (Voltage/Current)
CM1-AD04W is the AD module used to input 4 channel voltage and current.
CM1-AD08I has 8 channels Analog input (Current).
CM1-AD08V has 8 channels Analog input (Voltage).
CM1-AD08VI has 8 channels Analog input (Voltage/Current).
CM1-AD16VI has 16 channels Analog input (Voltage/Current).
AD04VI: 0–20 mA, 4–20 mA, 0–5 V, 1–5 V, -10–10 V, 0–10 V
AD04W: 0–20 mA, 4–20 mA, 0–5 V, 1–5 V, -10–10 V, 0–10 V
AD08I: 0–20 mA, 4–20 mA
AD08V: 0–5 V, 1–5 V, -10–10 V, 0–10 V
AD16VI: 0–20 mA, 4–20 mA, 0–5 V, 1–5 V, -10–10 V, 0–10 V
There are two AD conversion methods that user can choose:
Average processing 2. Sampling processing
Analog Input module converts input max and min value into 0–16000 (-8000–8000). If input value gets out of range, it is converted to -192–16191 (-8192–8191).
*AD04W: An input signal (0–20 mA, 4–20 mA, 0–5 V, 1–5 V, -10–10 V,
0–10 V) is converted to 3 formats of digital value as specified below;
A. Digital value: 0–64000 (or -32000–32000, 16-bit resolution of 1/64000)
B. Measuring value: see specification
C. Percentile value: 0–10000 (0–100.00%)
*AD08I can selectively use the digital values from the following options.
A. 192–16191 (0–65000)
B. -8192–8192 (-32768–32767)
C. 0–16000 (0–64000)
D. -8000–8000 (-32000–32000)
There is no limitation for the type of Analog modules installed on the base.
Normal status : LED On, Error status: LED blinking at 0.3 second interval.
6-1) CM1-AD04VI / AD08V / AD08I LED 상태 확인
LED | Status | Details |
RUN | ON | Always on when the power is ON (Normal state) |
OFF | Module Error (System error, contact service center) | |
| BLINK | Module Error (Refer to error codes) |
6-2) CM1-AD04W LED
LED | Status | Details |
RUN | ON | Always on when the power is ON (Normal status) |
OFF | Module Error (System error, contact service center) | |
ERR | ON | - |
OFF | Normal status | |
점멸 | Module Error (Refer to error codes) | |
CH1 ~ CH4 | ON | Detected an input signal |
OFF | Disconnected or detected an input signal of minimum value within the range | |
BLINK | Reached the alarm set value |
6-3) CM1-AD08VI / 16VI LED
LED | Status | Details |
RUN | ON | Initialization completed (Normal status) |
OFF | Not initialized or initialization failed | |
ERR | ON | Initializing |
OFF | Operating normally | |
BLINK | Module Error | |
CH1 ~ CH8 (CH1 ~CH16) | ON | Enable A/D conversion |
OFF | Disable A/D conversion | |