Expansion Configuration(CM1 Dualization)
▶ Settings for Expansion
Open CICON and click “PLC Parameter” in the Project Window.
Click “Enable” and select the number of expansion bases in the “Expansion” field (if number of expansion bases is different from the setting number, and error may occur.)
The module number is counted continually from the previous base.
▶ Recommendations on using USB Cable
Recommended to use CIMON’s shielded cable within 3m length.
In case of using PC that is vulnerable to noises, it is recommended to use a USB Hub or Isolator.
USB Loader connection is only available with XPnF/S.
▶ After connection from Local Base to Expansion Base, select the number of bases in the sequence.
< EP0nA Module > |
| < EP02F/G Module with XP1S, XPnF, UPnF CPU > | |||
No. of Bases | Rotary Switch |
| No. of Bases | Rotary Switch | Rotary Switch |
Exp No. 1 | 1 |
| Exp No. 1 | 0 | 1 |
Exp No. 2 | 2 |
| Exp No. 2 | 0 | 2 |
Exp No. 3 | 3 |
| Exp No. 3 | 0 | 3 |
Exp No. 4 | 4 |
| … | … | … |
… | … |
| Exp No. 16 | 1 | 6 |
Exp No. 14 | D |
| … | … | … |
Exp No. 15 | E |
| Exp No. 30 | 3 | 0 |
Exp No. 16 | F |
| Exp No. 31 | 3 | 1 |
< EP02F/G Module with XP1S, XPnF, UPnF CPU>
No. of Bases | 슬롯 번호 |
Exp No. 1 | 0 |
Exp No. 2 | 1 |
Exp No. 3 | 2 |
Exp No. 4 | 3 |
|
|
… | … |
Exp No. 15 | E |
Exp No. 16 | F |
▶ Slot number of “FROM” and “TO” command
Slot number starts from 0.
Format: h + [Base No.] + [Slot No.]
h: Hexadecimal number
Base No: Hexadecimal number 2 Characters
Slot No: Hexadecimal number 2 Characters
Example)
No. of Base | No. of Slot | Format |
Local Base | 5 | h0005 or 5 |
Expansion No. 1 | 0 | h0100 |
Expansion No. 2 | 3 | h0203 |
Expansion No. 9 | 8 | h0908 |
Expansion No. 10 | 9 | h0A09 |
Expansion No. 15 | 10 | h0F0A |
Expansion No. 16 | 11 | h100B |