General Specifications(CM3 DIO)
Items | Specification | Standards | |||||||
Ambient Temp. | -10℃–65℃ | - | |||||||
Storage Temp. | -25℃–80℃ | - | |||||||
Ambient Humidity | 5–95% RH, Not Condensed | - | |||||||
Storage Humidity | 5–95% RH, Not Condensed | - | |||||||
Vibration | For Discontinuous Vibration | IEC 61131-2 | |||||||
Frequency | Acceleration | Amplitude | Times | ||||||
5 ≤ f < 9 Hz | - | 3.5 mm | X, Y, Z Each direction, 10 times | ||||||
9 ≤ f ≤ 150 Hz | 9.8 m/s2 (1G) | - | |||||||
Continuous Vibration | |||||||||
Frequency | Acceleration | Amplitude | Times | ||||||
5 ≤ f < 9 Hz | - | 1.75 mm | X, Y, Z Each direction, 10 times | ||||||
9 ≤ f ≤ 150 Hz | 4.9 m/s2 (0.5G) | - | |||||||
Shock | Max. impact acceleration: 147 m/s2 (15G) Authorized time: 11 ms Pulse wave: Sign half-wave pulse (3 times each in X, Y, Z) | IEC 61131-2 | |||||||
Noise | Square Wave Impulse Noise | ±2 kV | CIMON Standard | ||||||
Electrostatic Discharge | Voltage: ±4 kV (contact), ±8 kV (air) | IEC 61131-2 IEC 61000-4-2 | |||||||
Radiated Electromagnetic Field Noise | 80–1000 MHz, 10 V/m | IEC 61131-2 IEC 61000-4-3 | |||||||
Fast Transient Burst Noise | Unit | Power Module | Digital I/O (24 V or more) | Digital I/O (less than 24V) Analog I/O Comm. interface | IEC61131-2 IEC61000-4-4 | ||||
Voltage | 2 kV | 2 kV | 1 kV | ||||||
Ambient Conditions | No corrosive gas or dust |
| |||||||
Altitude | 2,000 m or less |
| |||||||
Pollution | Pollution Degree 2 or less |
| |||||||
Cooling Type | Natural air cooling |
|