Items | CM1-RD04A | CM1-RD04B | |
Available RTD | Pt100 (JIS C1640-1989, JPt100 (KS C1603-1991, | Pt1000 (DIN EN60751) Ni1000 (DIN 43760) Ni1000 (TCR 5000) | |
Range of Temp. Input | Pt100: -200℃–600℃ (18.48 Ω–319.59 Ω) JPt100: -200℃–600℃ (17.14 Ω–317.28 Ω) | Pt1000: -200℃–600℃ (184.8 Ω–3135.9 Ω) Ni1000 (DIN 43760): -50℃–160℃ (742.6 Ω–1986.3 Ω) Ni1000 (TCR 5000): -50℃–160℃ (790.9 Ω–1799.3 Ω) | |
Digital Conversion | Digital converted value (14-bit): Digital converted value (16-bit): (First decimal place value*10) | Digital converted value: Detected temperature value: -2000–6000 (First decimal place value*10) | |
Detecting the Breaking of Wires | 3 wires per channel | ||
Accuracy | ±0.1% (Full Scale) | ||
Max. Conversion Rate | 50 ms/1Ch | ||
Number of Temp. inputs | 4 Ch/1 module | ||
Insulation | Between input terminal and PLC Power: Photocoupler Between channels: No | ||
Contact Terminal | 18-point Terminal Block | ||
Num. of Occupied Points | 16 Points | ||
Internal Current (mA) | +5 V | 50 | |
+15 V | 30 | ||
-15 V | 10 |