Allen Bradley MicroLogix Ethernet/IP

Allen Bradley MicroLogix Ethernet/IP

Communication Setup: Xpanel

I/O Device Configuration

To create a new device, select [Tools] → [I/O Device Editor]. Click the icon to add a new device, then select an “Ethernet” [Connection Type] and a “Allen-Bradly EthernNet/IP” [Device Type].

Device Name: Designate a name for the I/O Device.

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the [I/O Device Editor] window populates with the default settings for the selected communication protocol.

After selecting the correct [Connection Type] and [Device Type], match the remaining settings to the target I/O device’s communication settings.

See the Communication Configuration section for more information.

Communication Configuration

1. Ethernet IP Setup

  • Run RSLogix 500.

  • Select [Comms] → [Upload…] from the menu, and upload a project.

  • Double-click on [Channel Configuration] from the project window to open the ‘Channel Configuration’ window.

  • Go to the [Chan.1 - System] tab in the ‘Channel Configuration’ window.

  • Configure and save the IP Address, Subnet Mask, and Gateway Address.

  • Select [Comms] → [Download..], and download the setting to PLC.

Address and Function Codes

Address Format

Tag Type

Format

Example

Tag Type

Format

Example

Analog

[Symbol][Decimal Code]

X201 or Y300

Digital

[Symbol][Decimal Code]

E0201 or M9900

Supported Symbols

Symbol

Bit Range

Word Range

Name

Symbol

Bit Range

Word Range

Name

O

O:0.0/0 – O:30.255/15

O:0.0 – O:30.255

Output

I

I:0.0/0 – I:30.255/15

I:0.0 – I:30.255

Input

S

S:0/0 – S:163/15

S:0 – S:163

Status

B

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

Binary

N

N7:0/0 – N7:255/15

N9:0/0 – N255:255/15

N7:0 – N7:255

N9:0 – N255:255

Integer

F

 

F8:0 – F255:255

  • Registration is allowed in Float only.

Float

L

 

L9:0 – L255:255

  • Registration is allowed in UINT32, INT32 only.

Long

ST

 

ST9:0 – ST255:255

String

T

T4:0.0/0 – T4:255.2/15

T9:0.0/0 – T255:255.2/15

 

Txx:nn.0/15 = Enable(EN)

Txx:nn.0/14 = Timer Timing(TT)

Txx:nn.0/13 = Done(DN)

T4:0.0 – T4:255.2

T9:0.0 – T255:255.2

 

Txx:nn.1 = Preset Value(PRE)

Txx:nn.2 = Accumulated Value(ACC)

Timer

C

C5:0.0/0 – C5:255.2/15

C9:0.0/0 – C255:255.2/15

 

Cxx:nn.0/15 = Count up enable(CU)

Cxx:nn.0/14 = Count down enable(CD)

Cxx:nn.0/13 = Done(DN)

Cxx:nn.0/12 = Overflow(OV)

Cxx:nn.0/11 = Underflowt(UN)

Cxx:nn.0/10 = Update Accumulator(UA)

C5:0.0 – C5:255.2

C9:0.0 – C255:255.2

 

Cxx:nn.1 = Preset (PRE)

Cxx:nn.2 = Accumulated Value(ACC)

Counter

R

R6:0.0/0 – C6:255.2/15

R9:0.0/0 – R255:255.2/15

 

Rxx:nn.0/15 = Enable(EN)

Rxx:nn.0/14 =Update Enable(EU)

Rxx:nn.0/13 = Done(DN)

Rxx:nn.0/12 = Stack Empty(EM)

Rxx:nn.0/11 = Error(ER)

Rxx:nn.0/10 = Upload(UL)

Rxx:nn.0/9 = Inhibit(IN)

Rxx:nn.0/8 = Found(FD)

R6:0.0 – R6:255.2

R9:0.0 – R255:255.2

 

Rxx:nn.1 = Length value

Rxx:nn.2 = position value

Control

Communication Cable Wiring

This is an interface for communication between the TOUCH/PPC and the Device by Ethernet. This complies with IEEE802.3 for 10Base/100BaseTX. Refer to the PIN number and cable for RJ45 as shown below.

RJ45 Connector

RJ45 Jack

Direct Cable: Host ↔︎ HUB

Cable

No

Color

Color

No

Cable

 

 

 

1

Orange/White

Orange/White

1

 

 

 

 

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host ↔︎ Host

Cable

No

Color

Color

No

Cable

 

 

 

1

Orange/White

Green/White

1

 

 

 

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8