Create a new device | To configure the communication device of LSIS PLC, select [Tools] - [I/O Devices] or click the The ‘I/O Device Configuration’ dialog box will pop up. Click the [New Device] button. ![]() I/O Device Name: Give a device name. The Device Name will be used in the Station Name and Tag Configuration of the database. |
Select a device type | After selecting [Ok] in the previous step, the ‘Serial Communication Configuration’ dialog box will pop up as shown below. ![]() Select ‘Fatek PLC Cnet’ from the ‘Device Type’ dropdown menu, and choose the appropriate communication parameters. Those parameters must be matched with the PLC. |
Create a station | Move to the [Station] tab in the ‘Serial Communication Configuration’ dialog box and click [Add Station]. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel. ![]() Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the Device Name . Station Type: Choose the 'FATEK PLC' (no other type can be selected). Network ID: This field has no meaning in this driver (ignored in runtime). Station No.: Specify a decimal number between 0 and 126. 16Bit Data Swap: This field has no effect. 32Bit Data Swap: This field has no effect. Using Checksum: This field has no effect. This communication driver always checks the box. Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. |
Run ‘WinProLadder’.
Select [PLC] - [On-Line] from the menu.
Select ‘RS232' in the ‘Connection Name’ field, and push [Auto Check] to open the ‘Connect Auto Check’ window.
Select serial port on ‘Select Port No'.
Select PLC Type on ‘Select PLC Series’.
Select PLC side port on ‘Select Port’.
Press [OK] to do the connection auto check.
Now that the connection is finished, select [PLC] → [Setting] → [Station Number] to popup the ‘Station Number’ window.
After inputting the PLC station number, press [OK].
Select the port parameters on [PLC] → [Setting].
Select ‘Fatek Communication Protocal’ on Protocol.
After finishing the parameter settings, press the [OK] button.
If you use a serial loader port, check Port0 parameter on [PLC] → [Setting].
(1) Word tag is supported by 16-Bit only.
(2) Digital address is used only for digital tags.
(3) 32-Bit address is used only for 32-Bit analog tags.