  1. TC module can connect 8 types of Thermocouple (K, J, E, T, R, S, B, N) directly and indicate converted temperature as Celsius or Fahrenheit (℃, ℉). It can convert temperature value into digital value up to the first decimal place.

  1. TC module converts temperature data into 16bit binary digital value. It Converts maximum and minimum value of Thermocouple into 0~16,000 (-8,000 ~ 8,000).

  1. It indicates temperature from minimum -50℃ to maimum+50℃ and digital value -192 ~ 16191.

  1. If minimum and maximum value are set up, TC module converts minimum value into 0(-8,000) and maximum value into 16,000(8,000)

  1. Each channel of TC module can detect disconnection of thermocouple and cable and excess of measuring range.

  1. TC04A has 4 channels for Thermocouple.

  1. There is no limitation for number of TC modules installed on the one base.

  1. LED is lighted in normal status, and blinks at the intervals of 0.3 second in error status.