Wiring and Power Supply (CM-eXT2-10W)

Wiring and Power Supply (CM-eXT2-10W)

Wiring

  • Make sure to check if the device’s power and external power supply is turned off before wiring, via a breaker, or similar unit. Failure to do so may cause electric shock or damage to the device.

  • Check the rated voltage of the product.

  • In case of terninal block connector type, make sure that power cord is connected properly.

 

Wiring Connecting the Xpanel Power Cord

  • If the power supply voltage exceeds the GP’s specified range, connect a voltage transformer.

  • Between the line and the ground, be sure to use a low noise power supply. If there is still an excessive amount of noise, connect a noise reducing transformer.

  • The power supply cord should not be bundled with or kept close to main circuit lines (high voltage, high current), or input/output signal lines.

  • Connect a surge absorber to handle power surges.

  • To reduce noise, make the power cord as short as possible. 

  • When inputting power to the product, be sure to check the polarity (+, -) marked on the product before connecting. Incorrect polarity may cause product failure or fire.

● To avoid a short caused by loose ring terminals be sure to use ring terminals with an insulating sleeve.

● When the FG terminal is connected, be sure the wire is grounded. Not grounding the Xpanel unit will result in excess noise and vibration.

● The torque required to tighten these screws is 0.678_0.813 lbf*ft (0.5–0.6 N•m)

● Wire Range : AWG 14 - 26 SOL/STR, Wire Type : Cu

● To avoid a short caused by loose ring terminals be sure to use ring terminals with an insulating sleeve.

● When the FG terminal is connected, be sure the wire is grounded. Not grounding the Xpanel unit will result in excess noise and vibration.

● The torque required to tighten these screws is 0.678_0.813 lbf*ft (0.5–0.6 N•m)

● Wire Range : AWG 14 - 26 SOL/STR, Wire Type : Cu

 