It has only one digital value from TC module. It is used to get only one digital value if the FB name is finished with "_S".
Variable Name | I/O | Type | Device |
BASE | Input | Word | Write Base number 0~16 |
SLOT | Input | Word | Write Slot number CM1 : 0 ~ 11 / CM2 : 1 ~ 4 / CM3 : 1 ~ 11 |
CH | Input | Word | Write Channel number. (Ex. Ch2 : Write 2) |
OUTPUT | Output | Word | Write Word type device address that you want to save the converted value (Except :X / F / TS / TC / CS / CC / S) |
If you write wrong SLOT number or BASE number, CPU will have an error.
System Library type
CM1_TC_S
CM1_TC_S
· | CM1_TC_S |
· | CM2_TC_S |
· | CM3_TC_S |
Buffer Memory Index
· | CM1 TC : 21 ~ 28 (Ch.1~8 : Digital conversion value) |
· | CM2 TC : 21 ~ 28 (Ch.1~8 : Digital conversion value) |
· | CM3 TC : 21 ~ 24 (Ch.1~4 : Digital conversion value) |
Example) CM1_TC_S
You can get a digital value from Ch4 at slot #0 in Local base and save it to D00. When it works, D00 will be turned ON.
Example) CM3_TC_S
You can get a digital value from Ch3 at slot #11 and save it to D00.
0 Comments