General Specifications(CM1 OPC Server)
Items | Specification | Standards | ||||
Op. Temp | -10℃–65℃ | - | ||||
St. Temp | -25℃–80℃ | - | ||||
Op. Hum | 5–95% RH, Not condensed | - | ||||
St. Hum | 5–95% RH, Not condensed | - | ||||
Vibration | In case of Intermittent Vibration | IEC 61131-2 | ||||
Frequency | Acceleration | Amplitude | Sweep | |||
5 ≤ f < 9 Hz | - | 3.5 mm | 10 times in X, Y, Z | |||
9 ≤ f ≤ 150 Hz | 9.8 m/s2(1G) | - | ||||
In case of Continuous Vibration | ||||||
Frequency | Acceleration | Amplitude | Sweep | |||
5 ≤ f < 9 Hz | - | 1.75 mm | 10 times in X, Y, Z | |||
9 ≤ f ≤ 150 Hz | 4.9 m/s2(1G) | - | ||||
Shock | Max. shock Acc.: 147m/s2(15G) Time: 11 ms Pulse wave: Half sine wave pulse (3 times in X, Y, Z) | IEC 61131-2 | ||||
Noise | Square Wave Impulse Noise | ±2 kV | CIMON Standard | |||
Electrostatic Discharge | ±4 kV (Contact), ±8 kV (Air) | IEC 61131-2 IEC 61000-4-2 | ||||
Radiated Electromagnetic field | 80–1000 MHz,10 V/m | IEC 61131-2 IEC 61000-4-3 | ||||
Fast Transient Burst Noise (Voltage) | CPU, Power | 2 kV | IEC 61131-2 IEC6 1000-4-4 | |||
Digital/Analog I/O (AC) | ||||||
Digital/Analog I/O (DC) | 1 kV | |||||
Communication | ||||||
Ambient Conditions | No corrosive gas and no dust | |||||
Altitude | 2,000 m or less | |||||
Pollution | Pollution Degree 2 or less | |||||
Cooling | Natural Air Cooling |