Communication Setup: PLC (GX Developer)

The following configuration is needed on the PLC side.

This can be done at the ‘PLC Parameter-Serial’ setup window of GX Developer as shown in the following picture.

  1. Enable the ‘Use serial communication’ option.

  2. Configure the communication speed. This configuration must match with the one of the Xpanel’s configuration.

  3. Configure the ‘Sum check' option. This option must match with the Xpanel’s configuration.

  4. Set ‘Transmission wait time’ appropriately. Typically, this item is set as ‘No waiting Time’.

  5. Enable the ‘Run while setting: Permit’ option which makes it possible for the operator to control the value of the PLC with the Xpanel.

  6. Be aware that the PLC parameters are applied only after the cold restart of the PLC system.

This communication driver was tested with a Q00 CPU.


These CPUs do not have special configuration items for loader port communication:

Q2(H) / Q6H / Q12H / Q25H CPU

This communication driver was tested with a Q12H CPU.

Communication Setup: Xpanel

Create a new device

 

For creating a new device, go to [Tools] → [ I/O Devices] or click on the (blue star) icon on the main toolbar. The 'I/O Device Configuration’ dialog box will pop up. Click the [New Device] button to open the 'I/O Device Selection’ dialog box.

I/O Device Name: Give a device name. This name will be used in the tag configuration window of the database accompanied by the ‘Station Name’.

Select a device type

 

After clicking the [Ok] button on the previous step, the 'Serial Communication Configuration’ dialog box will pop up.

Configure the properties according to the type of PLC CPU. Please notice that the communication parameter combination shown in the following box is the only one allowed in the Q series CPU programming port (regardless of the type of CPU, no other configuration is allowed).

 

Q00CPU / Q01CPU

If the connecting CPU type is Q00 or Q01, then select the 'MITSUBISHI MELSEC Q Loader (Q00/Q01)' as the device type.

Q2(H) / Q6H / Q12H / Q25H

 If the connecting CPU type is Q02(H), Q06H, Q12H, or Q25H, then select the 'MITSUBISHI MELSEC Q Loader (Q02/Q06/Q12/Q25)' as the device type.

Create a station

Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel.

Each field can be configured as follows:

Station Name: Q_CPU

This name will be used in the database window accompanied by the device name.

Station Type: Q00 CPU

Choose the type of connected PLC CPU. If the connecting CPU is Q01CPU, then choose "Q00CPU". These two CPUs have no difference in the Xpanel communication driver.

Network ID: This field has no effect.

Station No.: 0

This number has no meaning for this driver.

16Bit Data Swap: This field has no effect.

32Bit Data Swap: This field has no effect.

Using Checksum

This configuration should be matched with the same configuration item of the PLC CPU. Ensure that this option is checked with the same status on both sides (verify the check status of the 'Sum Check' item of GX Developer).

Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds.

Supported PLC Memories

Q00CPU / Q01CPU

Memory Area

Symbol

Range

Notation

Bit / Word

Input Relay

X

X0000-X07FF

16

Bit

Output Relay

Y

Y0000-Y07FF

16

Bit

Internal Relay

M

M0000-M8191

10

Bit

SM

SM0000-SM1023

10

Bit

Latch Relay

L

L0000-L2047

10

Bit

Link Relay

B

B0000-B07FF

16

Bit

SB

SB0000-SB07FF

16

Bit

Edge Relay

V

V0000-V1023

10

Bit

Annunciator

F

F0000-F1023

10

Bit

Timer Contact

TS

TS0000-TS0511

10

Bit

Timer Clear

TC

TC0000-TC0511

10

Bit

Timer Current Value

TN

TN0000-TN0511

10

Word

Counter Contact

CS

CS0000-CS0511

10

Bit

Counter Coil

CC

CC0000-CC0511

10

Bit

Counter Current Value

CN

CN0000-CN0511

10

Word

Data Register

Special Data Register

D

D00000-D11135

10

Word

SD

SD0000-SD1023

10

Word

Link Register

Special Link Register

W

W0000-W07FF

16

Word

SW

SW0000-SW03FF

16

Word

Q02(H) / Q06H / Q12H / Q25H

Memory Area

Symbol

Range

Notation

Bit / Word

Input Relay

X

X0000-X1FFF

16

Bit

Output Relay

Y

Y0000-Y1FFF

16

Bit

Internal Relay

M

M0000-M8191

10

Bit

SM

SM0000-SM1023

10

Bit

Latch Relay

L

L0000-L8191

10

Bit

Link Relay

B

B0000-B1FFF

16

Bit

Edge Relay

V

V0000-V2047

10

Bit

Annunciator

F

F0000-F2047

10

Bit

Timer Clear

TC

TC0000-TC2047

10

Bit

Timer Current Value

TN

TN0000-TN2047

10

Word

Counter Coil

CC

CC0000-CC1023

10

Bit

Counter Current Value

CN

CN0000-CN1023

10

Word

Data Register

Special Data Register

D

D00000-D12287

10

Word

SD

SD0000-SD2047

10

Word

Link Register

Special Link Register

W

W0000-W1FFF

16

Word

SW

SW0000-SW07FF

16

Word

Wiring Diagram

RS-232C

  • No labels