This driver uses a standard Ethernet connection to communicate with LSIS FEnet devices.

Communication Settings: Xpanel

I/O Device Configuration

To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select LSIS FEnet for Device Type.

I/O Device Settings

 

Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol.

After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings.

See the Ethernet Communication Configuration section for more information.

Communication Settings: PLC

  • The following image shows a screenshot of the ‘Network Manager’ of the XG5000 programming tool.

  • This window can be activated from the menu through [Tools] → [Network Manager].

  • Enter the PLC IP address. This address has to be registered in the I/O device settings of Canvas.

  • Set the appropriate values for the Subnet Mask and the Gateway which are provided by the network administrator of your system.

  • Select ‘XGT server’ from the dropdown menu of the driver section.

Address and Supported Symbols

The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.

The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.

Supported Symbols

XGK (XGK-CPU* / XBM / XBC)

Name

Symbol

Bit Range

Word Range

Access

Input/Output

P

P00000 - P2047F

P0000 - P2047

R/W

Binary

M

M00000 - M2047F

M0000 - M2047

R/W

Binary

L

L000000 - L11263F

L00000 - L11263

R/W

Non-Volatile Binary

K

K00000 - K4095F

K0000 - K4095

R/W

If the CPU is XGK, the bit range is "K00000 - K2047F" and the word range is "K0000 - K2047".

Status

F

F00000 - F2047F

F0000 - F2047

R

Timer

T

T0000 - T2047

-

R/W

Counter

C

C0000 - C2047

-

R/W

Control

S

-

-

-

Integer

D

-

D00000 - D32767

R/W

Index

R

-

R00000 - R32767

R/W

XBM does not support the R and ZR. XBC supports only R. (R and ZR are the same device in the XBC.)

Index

ZR

-

ZR00000 - ZR65535

R/W

XBM does not support the R and ZR. XBC supports only R. (R and ZR are the same device in the XBC.)

Timer - Current Count

T

-

T0000 - T2047

R/W

Counter - Current Count

C

-

C0000 - C2047

R/W

Comm. Data Register

N

-

N00000 - N21503

R/W

Integer

Z

-

Z000 - Z127

R/W

XGK (XGK-CPUSN / XGK-CPUHN / XGK-CPUUN)

Name

Symbol

Bit Range

Word Range

Access

Input/Output

P

P00000 - P4095F

P0000 - P4095

R/W

Binary

M

M00000 - M4095F

M0000 - M4095

R/W

Binary

L

L000000 - L11263F

L00000 - L11263

R/W

Non-Volatile Binary

K

K00000 - K4095F

K0000 - K4095

R/W

Status

F

F00000 - F4095F

F0000 - F4095

R

Timer

T

T0000 - T8191

-

R/W

Counter

C

C0000 - C4095

-

R/W

Control

S

-

S000 - S255

R/W

Integer

D

-

D000000 - D524287

R/W

If the CPU is XGK-CPUSN, the word range is "D000000 - D262143".

Index

R

-

R00000 - R32767

R/W

Index

ZR

-

ZR000000 - ZR524287

R/W

Timer - Current Count

T

-

T0000 - T8191

R/W

Counter - Current Count

C

-

C0000 - C4095

R/W

Comm. Data Register

N

-

N00000 - N21503

R/W

Integer

Z

-

Z000 - Z255

R/W

Special Module Register

U

-

U00.00 - U7F.31

R/W

If the CPU is XGK-CPUSN, the word range is "U00.00 - U3F.31".

Communication Cable Wiring

This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.

RJ45 Connector

RJ45 Jack

Direct Cable: Host ↔︎ HUB

Cable

No.

Color

Color

No.

Cable

1

Orange/White

Orange/White

1

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host ↔︎ Host

Cable

No.

Color

Color

No.

Cable

1

Orange/White

Green/White

1

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

  • No labels