This driver is used to connect a CIMON Xpanel with a KOYO DL06 PLC using RS-232C or RS-422/485.
Communication Setup: Xpanel
Create a new device | To create a new device, select 'Tools' → 'I/O Devices' in the menu or click the I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a network type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in the following picture: In this window, set the ‘Device Type’ to ‘KOYO DirectNet’ and configure the remaining serial communication parameters. Ensure that these parameters are matched with the device’s configuration. |
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box and click ‘Add Station’. The ‘Station’ dialog box will appear as shown below: Each field can be configured with the following rules: Station Name: Give a name to the PLC. This name will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Choose either ‘'DirectNet(HEX)’ or ‘DirectNet(ASCII)’, depending on the PLC configuration. Station No: Specify a decimal number between 1 and 247. This must match the station number of the PLC. 16-Bit Data Swap: N/A 32-Bit Data Swap: N/A String Data Swap: N/A Using Checksum: N/A Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. |
Device Range
Use the following format for device tags within the database:
Memory Type | Discrete Memory Reference (octal) | Word Memory Reference (octal) |
Input Point | X0 - X777 | V40400 - V40437 |
Output Point | Y0 - Y777 | V40500 - V40537 |
Control Relays | C0 - C1777 | V40600 - V40677 |
Special Relays | SP0 - SP777 | V41200 - V41237 |
Timer Current Values (Analog) | TA0 - TA377 | V0 - V377 |
Timer Status Bits | T0 - T377 | V41100 - V41117 |
Counter Current Values (Analog) | CTA0 - CTA177 | V1000 - V1177 |
Counter Status Bits | CT0 - CT177 | V41140 - V41147 |
Stage | S0 - S1777 | V41000 - V41017 |
Remote I/O | GX0 - GX3777 GY0 - GY3777 | V40000 - V40177 V40200 - V40377 |
The above table is based on documentation for the Koyo DL06.
If the model used is not a Koyo DL06, DL405, or DL205, then you can only use word memory (you cannot access individual bits).
Digital Tags
Example of word memory referencing:
V40000.15 - bit 15 of word 40000
V40000.0 - bit 0 of word 40000
Example of discrete memory referencing:
GX017 - word 17 in octal (15 in decimal) of the remote I/O