Communication Setup: Xpanel

Select [Tools] - [I/O Devices] or click the (blue star) icon from the Main Tool.

To create a device, see image below.

I/O Device Name: Give a device name.

I/O Device Type: Select ‘Ethernet Device’.

The Device Name will be used in the Station Name and Tag Configuration of the Database.

Select [Ok] for the ‘Ethernet Communication Configuration’ dialog box to appear.

Select ‘Allen Bradley MicroLogix EthernetIP’ from the Device Type the dropdown menu, and choose ‘TCP’ as the Protocol.

Move to the [Station] tab of the ‘Ethernet Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel.

Each field can be configured with the following rules:

Station Name

Give a name to the PLC. This name will be used in the database window accompanied with the ‘Device Name’.

Station Type

Choose the ‘MicroLogix’. (No other type)

Network ID

No effect.

Socket Port No.

 Default is set as 4481 for MicroLogix.

16Bit Data Swap

Data is obtained by switching between High and Low Byte in WORD data.

32Bit Data Swap

Data is obtained by switching between High and Low Byte in double WORD data.

String Data Swap

 Data is obtained by switching between High and Low Byte in the string data.

Comm. Error Message Pop Up

With this feature ON, the communication error message appears when Xpanel detects “Send/Receive” error. The error message will disappear after 5 seconds.

Fast Mode

No effect.

Fixed ATVXEL Socket Port

Enables the ATVXEL Socket Port No.

ATVXEL Socket Port No.

Choose a Socket Port No. for the Xpanel.

I/O Device Write Enable

Enable the device to write.

Data Request Size Limit

Enables the 'WORD' and ‘BIT’ boxes below. Input the maximum word and bit data desired.

Communication Configuration

1. Ethernet IP Setup

  • Run RSLogix 500.

  • Select [Comms] → [Upload…] from the menu, and upload a project.

  • Double-click on ‘Channel Configuration’ from the project window, and open Channel Configuration window.

  • Go to the ‘Chan.1 - System’ tab.

  • Configure and save the IP Address, Subnet Mask, and Gateway Address.

  • Select [Comms] → [Download..], and download the setting to PLC.

Address and Function Codes

Address Format

Supported Symbols

Communication Cable Wiring

This is an interface for communication between TOUCH/PPC and Device by Ethernet. This complies with IEEE802.3 for 10Base/100Base TX. Refer to the PIN number and cable for RJ45 as shown below.

Direct Cable: Host <-> HUB

Crossover Cable: Host <-> Host