This Driver supports communication between Xpanel and the OMRON RFID Reader V680 Series.
This Driver is developed to support the V680 Command, Antenna 1 for 1:N Communication.
Communication Setup: Xpanel
Create a new Device
| To create a new device, select ‘Tools’ → ’I/O Devices’ or click the icon in the toolbar. The following picture shows the first step in creating a new device: I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in the following picture: Select ‘OMRON RFID Reader’ as the ‘Device Type’, and set the communication parameters as shown below (This is when pin 9 of the RFID SW3 configuration is ON (1:N Communication), and the rest of the pins are OFF). Baud Rate: 9600 Parity: Even Data Bit: 7 Stop Bit: 2 Bits RTS/CTS: OFF Comm. Type: RS232 |
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules: Station Name: Designate a name for the station. This will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Select ‘V680’ (This is the only available option). Network ID: N/A Station No: Enter the station number used by the communication module. This option must be set within the device configuration, and must match the number chosen here. The most likely default values are 0 or 1. 16-Bit Data Swap: N/A 32-Bit Data Swap: N/A Using Checksum: N/A Comm. Error Message pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. |