For creating a new device, go to [Tools] - [I/O Devices] or the (blue star) icon in the main toolbar.

I/O Device Name: Give a device name.

I/O Device Type: Select ‘Serial Device’.

The Device Name will be used in the Station Name and Tag Configuration of the Database.

Select [Ok] for the ‘Serial Communication Configuration’ dialog box to appear.

Select ‘Allen Bradley DF1’ from the Device Type the dropdown menu, and choose the appropriate parameters. These parameters should be matched with the PLC.

Communication parameters should be configured as shown in the following table.

Baud Rate

Must be matched with the one of PLC.

Parity

None

Data Bits

8 Bits

Stop Bits

1 Bit

Comm. Type

RS232

Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. All the connected PLC stations can be configured and registered to the Xpanel.

Each field can be configured with the following rules.

Station Name

Give a name to the PLC. This name will be used in the database window accompanied with the ‘Device Name’.

Station Type

Choose the ‘SLC500/MicroLogix’. (No other type can be selected.)

Network ID

This field has no meaning in this driver. (ignored in runtime)

Station No.

This number must be matched with the one of PLC.

16Bit Data Swap

This field has no meaning in this driver.

32Bit Data Swap

This field has no meaning in this driver.

Using Checksum

This field has no meaning in this driver.

Comm. Error Message Pop Up

If this item is checked, Xpanel displays a communication error notification message at every Rx and Tx error.

If the item is unchecked, Xpanel does not display the message at data receive error.

Only when there is data transmit (writing a TAG value to the station) error, the notification message is popped up. This message box will be closed automatically about 5 seconds later.

Communication Setup: RSLogix

The following picture shows a screenshot of the RSLogix channel configuration. The network address and communication speed (Baud Rate) of PLC are configured in this dialog box. ‘BCC' must be selected in the ‘Error Detection’ and ‘DF1 Full Duplex’ must be selected for the 'Driver’.

Please note that those set data should be matched with the device configuration of Xpanel.

Address Notation

The following table shows the list of devices that can be referenced in the Xpanel database.

Communication Cable Wiring