The address of a tag in Xpanel has the following format:

Tag Type

Format

Example

Analog

[Symbol][Decimal Number]

P023

Digital

[Symbol][Decimal Number][.][Hexadecimal Number]

P000.F

Symbol

Address

Description

Access

P

0001 - 1760

Parameter Area

The address of each tag can be induced from the parameter number of FC 300 or VLT 2800. For example, to monitor the ‘16-17 Speed [RPM]' of FC 300, the address should be designated with 'P1617’. For more parameters, please refer to the ‘How to Program’ section of the “FC 300 Design Guide”.

The value written to this address will be transferred to the FC 300 or VLT 2800 directly. That means parameters of the inverter can be modified by writing the desired value to this address. The new value can be stored to not only RAM, but also to EEPROM of FC 300. For storing a set value to the EEPROM, the C002 point must have a non-zero value.

R/W

C

000

Control Code

1 word-sized control data. Each bit has its own control meaning which is shown in the following ‘Control Code’ table. To control FC 300 or VLT 2800, write a value of the combination of the table.

Ensure that the reference (C001) is set as the desired value before issuing this control code.

W

001

Reference

This point is a signed word data (-32767 - +32767), and the range of data corresponds to -200% to +200% of reference. For example, the value of 16384 represents 100% of reference.

This reference value must be set before the actual control by control code (C000).

002

EEPROM Writing

If this is non-zero, the value written to the parameter area (Pnnnn) will be saved to the EEPROM as well as RAM of FC 300 or VLT 2800. Otherwise, the set value will be stored only in RAM. Ensure that this point is set as the desired value before parameter writing.

...

[C000 : Control Code for FC 300]

Bit No.

Bit Value = 0

Bit Value = 1

00

Reference value

External selection lsb

01

Reference value

External selection msb

02

DC brake

Ramp

03

Coasting

No coasting

04

Quick stop

Ramp

05

Freeze output

Use ramp

06

Ramp stop

Start

07

No function

Reset

08

No function

Jog

09

Ramp 1

Ramp 2

10

Data not valid

Data valid

11

Relay 01 open

Relay 01 active

12

Relay 02 open

Relay 02 active

13

Parameter set-up

Selection lsb

14

Parameter set-up

Selection msb

15

No function

Reverse

...

[C000 : Control Code for VLT2800]

Bit No.

Bit Value = 0

Bit Value = 1

00

 

Preset reference lsb

01

 

Preset reference msb

02

DC brake

 

03

Coasting stop

 

04

Quick stop

 

05

Freeze output frequency

 

06

Ramp stop

Start

07

 

Reset

08

 

Jog

09

Ramp 1

Ramp 2

10

Data not valid

Data valid

11

 

Relay 01 activated

12

 

Digital output terminal 46 activated

13

Selection setup, lsb

 

14

Selection setup, msb

 

15

 

Reverse

...