The communication Please note that Canvas can still communicate with these devices via Modbus if the specific protocol necessary for a given device is unavailable. For more information on a specific device type, refer to the Supported Communication Drivers section.
Once a new Serial I/O device has been added successfully, the three sections for configuration will appear as follow:
The General configuration page will appear after adding a serial device.
...
once a new Serial I/O device has been added successfully. An additional configuration is below the General configuration section and will differ based on the device protocol selected.
Table of Contents |
---|
Please refer to the following for additional information:
Child pages (Children Display) |
---|
General Configuration
Please know that general configuration will appear regardless of the selected Connection Type and Device Type.
...
Item | Description |
---|---|
Device Name | Allows the user to assign a name for the selected I/O |
device. |
Device Protocol |
Select the type of target device. This also selects the driver used to communicate with the device.
Time Out
The timeout feature periodically checks whether the connection is still valid. If a requested frame is not received in the assigned time, it will be processed as a communication failure. This option is not applied if the protocol is TCP/IP. Values represent multiples of 100ms. For example, a value of 10 represents 1000ms or 1 second.
Retry Count
Assign the number of communication retry attempts after a communication failure.
Serial Port
Select the COM port to be used by the local device (Xpanel). Each COM port may support different communication methods depending on the Xpanel model. You can choose a COM port number up to COM4 or a TTYMCX port up to TTYMCX4. Refer to the table below for more information.
Baudrate
Assign the baudrate. You can select a rate from 300 to 115,200 bps. The rate must be identical to the target device’s configuration.
Parity
Select an option for parity bit usage. Users may select none, even, or odd.
Data Bits
Assign the number of data bits per packet. This option must be equal to the target device’s configuration. Choosing 5 – 7 bits provides faster communication speed but can cause errors if the data contains Korean characters.
If Korean characters are included in the frames, select the 8-bit option.
Flow Control
Allows the user to enable or disable flow control.
Stop Bits
Select the number of bits used to signal the end of the frame. You can select 1 or 2 bits. This option must be identical to the setting on the target device.
Comm Type
Select the communication type used by the target device. You can select RS232, RS422, or RS485.
Station Number
Enter the station number of the target device.
※ Please refer to the corresponding driver manual for further configuration.
The following table lists the communication types supported by each COM port of different Xpanel models.
...
...
XT04
...
XT07
...
XT08
...
XT10
...
XT12
...
XT15
...
COM1
...
RS-232C
...
RS-232C
...
RS-232C
...
RS-422/485
...
RS-422/485
...
RS-422/485
...
COM2
...
RS-422/485
...
RS-422/485
...
RS-422/485
...
RS-232C
...
RS-232C
...
RS-232C
...
COM3
...
–
...
–
...
–
...
RS-232C
...
RS-232C
...
RS-232C
Device Specific Properties
Depending on the selected Device Protocol, the available properties in the PLC Type tab change, and a new tab unique to the device type may appear depending on the selection.
...
Item
...
Description
...
PLC Type
...
Allows the user to assign a specific model of PLC for the selected Device Protocol. This option is only enabled for the CIMON CI-bus, LSIS Cnet, and Mitsubishi MELSEC drivers.
...
Modbus RTU
...
The following properties are revealed when selecting the Modbus RTU option for the Device Protocol.
...
Swap 16
...
Enable/Disable 16-bit data swaps.
...
Swap 32
...
Enable/Disable 32-bit data swaps.
...
Swap String
...
Enable/Disable string swaps.
...
Melsec: Sum Check
...
Allows the user to enable or disable Sum Checks.
Station
Users can define the Station Name and Station Number of the selected Serial Device in the Station tab.
...
Allows the user to select a protocol for a device. | |
Timeout (ms) | The maximum time to wait with no response before assuming a communication failure. |
Retry Count | Set the number of retries for sending a frame when communication fails. |
Swap String | Swaps the upper and lower bytes of string word data. |
String Encoding | Specifies the encoding method for reading and writing string values stored on the device. This option can be overridden for individual tags in the Edit Tag menu. |
String Encoding Method | When an invalid character is encountered, the gateway will do one of the following:
|
Serial Port | Select a serial communication port for the Xpanel. COM1: RS422/485 |
Baudrate | 300-230400 bps is supported. The range may vary according to the I/O device. |
Parity | Select the same parity (None, Even, Odd) as the device. |
Data Bits | Select the same data bit setting (7 Bits, 8 Bits) as the device. |
Flow Control | The amount of data being transmitted to itself using the serial communication method can be turn On, Off, or Control. |
Stop Bits | Select the same stop bit setting (1-Bit or 2-Bit) as the device. |
Additional Configuration - Device Specific
Modbus RTU
...
Item | Description |
---|---|
Swap 16 | Denotes whether to swap the order of the BYTEs within each WORD when reading/writing INTEGER types with this device. |
Swap 32 | Denotes whether to swap the order of the WORDs within each DWORD when reading/writing INTEGER types with this device. |
Swap 64 | Denotes whether to swap the order of the DWORDs within each QWORD when reading/writing INTEGER types with this device. |
Swap String | Denotes whether to swap the order of the BYTEs within each WORD when reading/writing STRING types with this device. |
Swap Float 16 | Denotes whether to swap the order of the BYTEs within each WORD when reading/writing float (FLOAT32) types with this device. |
Swap Float 32 | Denotes whether to swap the order of the WORDs within each DWORD when reading/writing float (FLOAT32) types with this device. |
Swap Double 16 | Denotes whether to swap the order of the BYTEs within each WORD when reading/writing double (FLOAT64) types with this device. |
Swap Double 32 | Denotes whether to swap the order of the WORDs within each DWORD when reading/writing double (FLOAT64) types with this device. |
Swap Double 64 | Denotes whether to swap the order of the DWORDs within each QWORD when reading/writing double (FLOAT64) types with this device. |
Mitsubishi MELSEC Serial
...
Item | Description |
---|---|
Frame Type | Frame Type is used to verify that data in a packet was transmitted/received correctly. Only |
Station Configuration
This configuration page can be accessed by clicking Tools > I/O Device Editor… > select serial device, then click Station.
...
Item | Description |
Station Name | Enter the station name for the I/O device. |
Station Number | Set the station ID. It must match the target device’s station ID. |