Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Refer to the table below for available device ranges.

Symbol

Range

Size

Access

P

P0 - P63F

64

R/W

M

M0 - M203F

192

R/W

L

L0 - L63F

64

R/W

K

K0 - K31F

32

R/W

F

F0 - F63F

64

R

T

T0 - T256

256

R/W

C

C0 - C256

256

R/W

D

D0 -D9999

10000

R/W

S

S0 - S99

100

R/W

Communication Cable Wiring

RS-232C

RS-422

The wiring in the terminal resistance must be 330 Ω. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed.

RS-485

The wiring in the terminal resistance must be 120 Ω. When using RS-485, connect SDA and SDB, but disconnect RDA and RDB. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed.