For creating a new device, go to [Tools] - → [I/O Devices] or the icon in the main toolbar.
...
I/O Device Type: Select ‘Serial Device’. The Device Name device name will be used in the Station Name and Tag Configuration ‘Station Name’ and tag configuration of the Databasedatabase.
Select [Ok] for the ‘Serial Communication Configuration’ dialog box to appear.
...
Each field can be configured as followed:
Station Name | Give a name to the PLC. This name will be used in the database window accompanied by the ‘Device Name’. |
Station Type | Choose the ‘SLC500/MicroLogix’ (no other type can be selected). |
Network ID | This field has no meaning in this driver (ignored in runtime). |
Station No. | This number must be matched with the one of PLC. |
16Bit Data Swap | This field has no meaning in this driver. |
32Bit Data Swap | This field has no meaning in this driver. |
String Data Swap | This field has no meaning in this driver. |
Using Checksum | This field has no meaning in this driver. |
Comm. Error Message Pop Up | If When this item is checked, Xpanel displays a communication error message at box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display an error message. However, if there is an error when writing a tag value to the station value, the notification message will pop upmessage for communication errors. This message box will close automatically closes after 5 a few seconds. |
See the Communication Configuration section for more information about the remaining parameters.
Communication Setup: RSLogix
The following picture shows a screenshot of the RSLogix channel configuration. The network address and communication speed (Baud Rate) of the PLC are configured in this dialog box. ‘BCC' must be selected for the ‘Error Detection’ and ‘DF1 Full Duplex’ must be selected for the 'Driver’.
...
The following table shows the list of devices that can be referenced in the Xpanel database.
...
Symbol | Description | Word Notation | Bit Notation | Access |
I | Input File | I:00.000 – I:08.255 | I:00.000/00 – I:08.255/15 | R/W |
O | Output File | O:00.000 – O:08.255 |
| R/W |
S | Status File | S:0 – S163 | M31.7 | R/W |
B | Bit File | B3:0 – B3:255 | SM85.7 | R/W |
T | Timer File | T4:0 – T4:255 | T127 | R/W |
C | Counter File | C5:0 – C5:255 | C127 | R/W |
N | Integer File | N7:0 – N7:255 | - | R/W |
F | Float File | F8:0 – F8:255 | - | R/W |
Communication Cable Wiring
...