Create a new device
| In order to create a new device, select [Tools] → [I/O Devices] or click the I/O Device Name: Select a device name. This name will be used in the tag configuration window of the database, accompanied by the ‘Station Name’. |
Select a device type | After clicking [Ok] on the previous step, the ‘Serial Communication Configuration’ dialog box will pop up. Device Type: ATIVAaltusGR Comm. Port: COM1 Select the port number. If COM1 is selected, only RS-232C will work. Other serial communication cannot work while RS-232C is working. Baud Rate: 9,600 In order to communicate with the serial port of Altus PLC, the baud rate must be set to 9,600. Otherwise, the communication will fail. Parity: Even Data bits: 8 bits Stop bits: 1 bit RTS/CTS: OFF Comm. Type: RS-232C See the Communication Configuration section for more information about the remaining parameters. |
Create a station | Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel. Station Name: If there are many devices to communicate with Xpanel, the station name distinguishes between devices. It shows “Device.Station” such as “GR350.STAT”. Station Type: ATIVAaltusGR (no other option available). Network ID: It is not editable. Station Number: 0. It must be the same as the device’s station number. See the Communication Configuration section for more information about the remaining parameters. |
...